1. Confirm the specifications.

Products represented in this catalog are designed for use in 
compressed air appllications only (including vacuum), unless 
otherwise indicated.
Do not use the product outside their design parameters.
Please contact SMC when using the products in applications 
other than compressed air (including vacuum).

4. Use clean air

If the compressed air supply is contaminated with chemicals, 
cynthetic materials, corrosive gas, etc., it may lead to break 
down or malfunction.

Selection

Mounting

Piping

Air Supply

Maintenance

Operating Environment

Warning

1. Instruction manual

Install the products and operate them only after reading the 
instruction manual carefully and understanding its contents. 
Also keep the manual where it can be referred to as 
necessary.

2. Securing the space for maintenance

When installing the products, please allow access for 
maintenance.

3. Tightening  torque

When installing the products, please follow the listed torque 
specifications.

Warning

1. Do not use in environments where the product 

is directly exposed to corrosive gases, 
chemicals, salt water, water or steam.

2. Do not expose the product to direct sunlight 

for an extended period of time.

3. Do not use in a place subject to heavy 

vibrations and/or shocks.

4. Do not mount the product in locations where it 

is exposed to radiant heat.

Warning

1. Maintenance procedures are outlined in the 

operation manual.

Not following proper procedures could cause the product to 
malfunction and could lead to damage to the equipment or 
machine.

2. Maintenance work

If handled improperly, compressed air can be dangerous.
Assembly, handling and repair of pneumatic systems should 
be performed by qualified personnel only.

3. Drain flushing

Remove drainage from air filters regularly. (Refer to the 
specifications.)

4. Shut-down before maintenance

Before attempting any kind of maintenance make sure the 
supply pressure is shut of and all residual air pressure is 
released from the system to be worked on.

5. Start-up after maintenance and inspection

Apply operating pressure and power to the equipment and 
check for proper operation and possible air leaks. If operation 
is abnormal, please verify product set-up parameters.

6. Do not make any modifications to be product.

Do not take the product apart.

Warning

1. Before piping

Make sure that all debris, cutting oil, dust, etc, are removed 
from the piping.

2. Wrapping of pipe tape

When screwing piping or fittings into ports, ensure that chips 
from the pipe threads or sealing material do not get inside the 
piping. Also, when the pipe tape is used, leave 1.5 to 2 thread 
ridges exposed at the end of the threads.

Caution

1. Operating fluid

Please consult with SMC when using the product in 
applications other than compressed air (including vacuum).
Regarding products for general fluid, please ask SMC about 
applicable fluids.

2. Install an air dryer, aftercooler, etc.

Excessive condensate in a compressed air system may cause 
valves and other pneumatic equipment to malfunction.
Installation of an air dryer, after cooler etc. is recommended.

3. Drain flushing

If condensate in the drain bowl is not emptied on a regular 
basis, the bowl will over flow and allow the condensate to 
enter the compressed air lines.
If the drain bowl is difficult to check and remove, it is 
recommended that a drain bowl with the auto-drain option be 
installed.
For compressed air quality, refer to “Air Preparation 
Equipment” catalog.

Warning

Common Precautions

Be sure to read before handling.
For detailed precautions on every series, refer to main text.

16-14-4

Summary of Contents for ISE30 Series

Page 1: ...ht type Elbow type High Precision 2 color Display Digital Pressure Switch Series ZSE30 ISE30 With One touch fittings are newly introduced 16 2 1 ZSE ISE PSE Z I SE3 PS Z I SE1 2 ZSP ISA2 IS ZSM PF2 IF...

Page 2: ...oose the setting according to your application requirements 4 different display settings are available 17 8 mm reduction Straight type 12 4 mm reduction Elbow type Comparison when One touch fittings K...

Page 3: ...ed for stackable displays which can be mounted either horizontally or vertically 126 40 More user friendly controls Each display required its own panel opening New Model ZSE30 ISE30 Vacuum Low pressur...

Page 4: ...ions Nil M With unit switching function Fixed SI unit International System of Units Note Note Fixed unit For vacuum Low pressure kPA For positive pressure MPa NPN output PNP output 1 to 5 V output 4 t...

Page 5: ...t from 0 3 1 2 digit 7 segment indicator 2 color display Red and green Sampling cycle 5 times s Light up when output is ON Green 2 F S or less based on 25 C IP40 Operating 0 to 50 C Stored 10 to 60 C...

Page 6: ...OWN button to select a newly desired operating Select the color for LCD display Press the UP or DOWN button to choose a display color Press the SET button to set the color and proceed to the operating...

Page 7: ...oth the UP and DOWN buttons simultaneously to return to the measuring mode 2 Auto preset setting Press the SET button to activate the mode to execute auto preset functions When is displayed start the...

Page 8: ...utton and hold for 4 seconds or longer to display the current setting and select the mode Zero out Zero ADJ function This function clears and resets the displayed value as long as the measuring pressu...

Page 9: ...tch operation status UP button SET button 25 NPN open collector output Maximum 30 V 80 mA Residual voltage 1 V or less 26 Analog output type 1 to 5 V 2 5 F S Output impedance 1 k 28 Analog output type...

Page 10: ...2 M3 x 0 5 Thread depth 4 Lead wire with connector M5 x 0 8 A B C A B With One touch fitting Straight Elbow One touch fitting size 4 5 32 6 1 4 Straight A 14 4 B 11 2 A 20 22 4 22 8 B 10 4 12 8 13 2...

Page 11: ...E IN JAPAN 8 17 8 7 2 8 75 9 5 Panel thickness 0 5 to 6 SET MPa PRESSURE OUT 11 34 5 42 4 Panel thickness 0 5 to 6 17 8 8 9 5 Panel mount 16 2 11 ZSE ISE PSE Z I SE3 PS Z I SE1 2 ZSP ISA2 IS ZSM PF2 I...

Page 12: ...ons Panel fitting dimension MADE IN JAPAN MADE IN JAPAN MADE IN JAPAN MADE IN JAPAN MADE IN JAPAN MADE IN JAPAN 31 x n pcs 3 5 x n pcs 1 31 24 and up 0 0 4 31 24 and up 31 x n pcs 3 5 x n pcs 1 0 0 4...

Page 13: ...its connector when the power is on A switch output malfunction may occur 3 Wire separately from power lines and high voltage lines avoiding wiring in the same conduit with these lines Malfunctions ma...

Page 14: ...ube One touch fitting Regulating Pressure Range and Rated Pressure Range Set the pressure within the rated pressure range The regulating pressure range is the range of pressure that is possible in set...

Page 15: ...experienced operators 3 Do not service machinery equipment or attempt to remove components until safety is confirmed 1 Inspection and maintenance of machinery equipment should only be performed once...

Page 16: ...qualified personnel only 3 Drain flushing Remove drainage from air filters regularly Refer to the specifications 4 Shut down before maintenance Before attempting any kind of maintenance make sure the...

Page 17: ...an international standard related to environmental management systems and environmental inspections While promoting environmentally friendly automation technology SMC is also making diligent efforts t...

Page 18: ...chinery Directive The Machinery Directive contains essential health and safety requirements for machinery as applied to industrial machines e g machine tools injection molding machines and automatic m...

Page 19: ...tion OSHA SMC was tested for compliance with CSA Standards and UL Standards at the same time and was approved for compliance with the two Standards The above CSA NRTL C logo is described on a product...

Page 20: ...COLOMBIA Distributor Airmatic Ltda Calle 18 69 05 Apart Aereo 081045 Santa Fe de Bogot Colombia TEL 1 424 9240 FAX 1 424 9260 U K SMC Pneumatics U K Ltd Vincent Avenue Crownhill Milton Keynes MK8 0AN...

Page 21: ...lvia Park Road Mt Wellington Auckland New Zealand TEL 09 573 7007 FAX 09 573 7002 TAIWAN SMC Pneumatics Taiwan Co Ltd 17 Lane 205 Nansan Rd Sec 2 Luzhu Hsiang Taoyuan Hsien TAIWAN TEL 03 322 3443 FAX...

Page 22: ...3 step setting step setting 3 step setting Push Push Push Finish setting 3 Push Push Push 1 2 Adjust to set value with buttons Added vacuum range P Rated pressure range 0 0 to 101 0 kPa 2 added outpu...

Page 23: ...001 MPa 0 1 kPa 500 kPa 500 kPa 0 1 kPa NPN or PNP open collector 1 output NPN or PNP open collector 2 outputs NPN or PNP open collector 1 output Analog output voltage or current Output R1 8 NPT1 8 M5...

Page 24: ...mber of core of lead wires will be 3 and for other types it will be 4 With unit display Note 1 switching function Fixed SI unit Note 2 With unit display Note 1 switching function Initial value psi Nil...

Page 25: ...cannot be used together Note 3 When analog current output is selected analog voltage output cannot be used together Model ZSE30A Vacuum pressure Rated pressure range Set pressure range Withstand press...

Page 26: ...the primary pressure by adjusting the response time Can convert the display value Reduces power consumption Converts display resolution from the normal value of 1 1000 to 1 100 It reduces the monitor...

Page 27: ...uit Main circuit Internal Circuits and Wiring Examples Max 80 mA Residual voltage 1 V or less Max 28 V 80 mA Residual voltage 1 V or less Max 80 mA Residual voltage 1 V or less Max 28 V 80 mA Residual...

Page 28: ...ual voltage 1 V or less Analog current output Max load impedance Power supply voltage 12 V 300 Power supply voltage 24 V 600 Min load impedance 50 Max 28 V 80 mA Residual voltage 1 V or less Analog vo...

Page 29: ...8 N01 NPT1 8 20 0 1 2 x M3 x 0 5 thread depth 4 M5 x 0 8 Width across flats 12 20 0 1 17 55 9 8 14 10 85 20 7 15 6 9 3 10 85 14 17 95 10 10 85 22 85 16 1 11 6 10 85 21 75 10 3 14 10 85 23 45 16 1 12 1...

Page 30: ...2 9 6 14 7 30 34 6 25 42 5 A Bracket C Option unit part no ZS 38 A3 A3 20 30 20 45 5 5 7 5 20 7 2 5 2 9 1 13 6 5 2 B 30 1 6 25 Z ISE30A F Option 2 Bracket A Option unit part no ZS 38 A1 A1 Bracket B...

Page 31: ...8 9 5 R4 5 47 8 R4 5 21 33 5 33 5 42 4 11 17 8 8 9 5 Panel thickness 0 5 to 6 Panel mount Z ISE30A F Option 2 Panel mount adapter Option unit part no ZS 27 C B Panel mount adapter Front protection co...

Page 32: ...4 x R 2 o r l e s s 31 0 0 4 31 0 0 4 24 or more 31 x n pcs 3 5 x n pcs 1 4 x R2 or less 31 0 0 4 24 or more 31 x n pcs 3 5 x n pcs 1 4 x R2 or less 31 0 0 4 9 Series ZSE30A F ISE30A Multiple 2 pcs or...

Page 33: ...m the measured pressure The optimum set value is determined automatically by repeating vacuum and break with the target workpiece several times Fine adjustment of the indicated value of the pressure s...

Page 34: ...pressure error Applied pressure error System error Solution Load current of switch output OUT1 exceeds 80 mA Shut off the power supply After eliminating the out put factor that caused the excess curre...

Page 35: ...ions specifications and lead times M12 4 pin pre wired connector Lead wire length 100 mm 1 How to Order ZSE30A F ISE30A X510 Output specifications A NPN open collector 2 outputs B PNP open collector 2...

Page 36: ...ay occur due to noise from these other lines 2 If a commercial switching regulator is used make sure that the F G terminal is grounded Caution 1 This pressure switch is CE marked however it is not equ...

Page 37: ...et pressure range Caution Set Pressure Range and Rated Pressure Range Rated pressure range of switch Set pressure range of switch Switch 100 kPa 0 100 kPa 500 kPa 1 MPa Pressure range ZSE30AF ISE30A 1...

Page 38: ...iodical checks to confirm proper operation Warning Limited warranty and Disclaimer Compliance Requirements The product used is subject to the following Limited warranty and Disclaimer and Compliance R...

Reviews: