HRX-OM-Q033
Chapter 4 MODBUS communication function
4.10
Register Map
HRSH Series
4-20
Bit
Name
Explanation
A
lar
m f
lag
3
0
Unused
Alarm given off status
0= Not occurred
1= Occurred
1
Unused
2
Unused
3
Unused
4
Compressor discharge temp. sensor
failure
5
Compressor discharge temp. rise
6
Internal unit fan stoppage
7
Dust-proof filter maintenance
1
8
Power stoppage
9
Compressor waiting
10
Fan breaker trip
1
11
Fan inverter error
1
12
Compressor breaker trip
2
13
Compressor inverter error
14
Pump breaker trip
2
15
Pump inverter error
A
lar
m f
lag
4
0
Air exhaust fan stoppage
3
1
Unused
2
Unused
3
Unused
4
Unused
5
Unused
6
Unused
7
Unused
8
Unused
9
Unused
10
Unused
11
Unused
12
Unused
13
Unused
14
Unused
15
Unused
1: These alarms do not occur on the product of the cooling method
‘-W’.
2: These alarms do not occur on the product of the power specification '-20'.
3: These alarms do not occur on the product of the cooling method
‘-A’.
・
The current alarm flag bit assignment will be changed in the future due to the addition of
optional functions.
・
Unused bit is fixed to 0.