HRX-OM-Q033
Chapter 2 Contact input/output communication
2.5
Contact input signal
HRSH Series
2-16
2.5 Contact input signal
There are two contact input signals. As the default condition, contact input
signal 1 is used for run/stop signal (signal type: alternate), and contact input
signal 2 is not used. The input signals can be customized depending on the
customer’s application.
Table 2.5-1
Contact input signal
Class of signal
Signal configuration
Timer
Default
setting
Description
Display
Description
Display
Delay
timer of
reading
OFF
detection
Contact input
signal 1
Run/stop
signal input
RUN
Alternate
ALT
-
-
○
Momentary
MT
-
-
External switch
signal
input
(N.O)
SW_A
Alternate
ALT
Used
Used
External switch
signal
input
(N.C)
SW_B
Alternate
ALT
Used
Used
Without signal
input
OFF
-
-
-
-
Contact input
signal 2
Run/stop
signal input
RUN
Alternate
ALT
-
-
Momentary
MT
-
-
External switch
signal
input
(N.O)
SW_A
Alternate
ALT
Used
Used
External switch
signal
input
(N.C)
SW_B
Alternate
ALT
Used
Used
Remote signal
input
RMT
Alternate
ALT
-
-
Momentary
MT
-
-
Without signal
input
OFF
-
-
-
-
○
2.5.1
Run/stop signal input
・
Remote signal input
1)
Run/stop signal input (Signal type: Alternate)
The product keeps operating while the input signal from the customer is ON.
2)
Run/stop signal input (Signal type: Momentary)
The state changes when the input signal from the customer goes OFF. This signal operates while
the product is stopped, and stops while the product is being operated. Maintain the ON condition
for 300ms or longer.
OFF
ON
Run
Stop
Product condition
Run/stop signal input
(
Momentar
y
)
300ms
300ms
OFF
ON
Run
Stop
Product condition
Run/stop
signal input
(
Alternate
)
Summary of Contents for HRSH Series
Page 5: ...HRX OM Q033 Contents HRSH Series 6 3 2 Setting and checking 6 3...
Page 6: ......
Page 56: ......
Page 83: ......