Error! Style not defined.
-9
Electrical wiring diagram
Fig. 3-6 How to set up (electrical wiring)
Use separate cables for power supply and signal lines.
R e m a r k s
DC24V
24COM
2
3
5
1
3.9k
Ω
7
4
6
8
9
1
0
SD
+
SD-
Terminal stand(14 poles)
RS-485
communicat
ions
(Option)
Warning signal
(contact output)
Run signal output
(contact output)
Fault signal output
(contact output)
Remote operation
Signal input
(Contact input)
Customer's Epuipment
side
Electrical unit
(Thermo-cooler side)
Name
Operation
Close:Run
Open:Stop
Run
:
Close
Stop
:
FOpen
Power supply shut
off
:
FOpen
Nomal:Close
Warning
:
Open
Power supply shut
off
:
Close
-
Specification
maximum load current
:
DC24V 1A
minimum load current
:
DC5V 10mA
Communication protocol
:
Compliant EIA standard
RS-485
Direction of infomation
:
Half duplex
Synchronization method
:
Asynchronous
Nomal:Close
Fault
:
Open
Power supply shut
off
:
Close
Rated voltage
:
DC24V
±
10%
Maximum load current
:
35mA
maximum load current
:
DC24V 1A
minimum load current
:
DC5V 100mA
maximum load current
:
DC24V 1A
minimum load current
:
DC5V 10mA
internal
circuit
internal
circuit
Open