-11-
No.EX
※※
-OMH0025-C
Product Selection
■
Selection for low wattage and high wattage load
The type is selected based on the SI unit type and the current consumption of the connect load.
•EX126 and EX250 series (excluding the one power supply system for AS-i)
The Output block for low wattage load should not be used when the current consumption of the connected
output equipment (load) is above the rated current of 62 mA (1.5 W, 24 VDC).
If used, the SI unit will malfunction.
The Output block for high wattage load and a Power block must be used when the current consumption
exceeds the rated load current of 62 mA.
[Example]
○: This is possible to use it.
×
: This is not possible to use it.
Current consumption of the load
(output equipment)
62 mA or less
Use Output block for low wattage load
Above 62 mA
Use Output block for high wattage load + Power block