Output connector (MIL20pin) pin assignment (EX510-S 02 )
•
EX510-S002
Terminal No.
1 3 5 7 9 11
13 15 17
19
Output
No. 0 2 4 6 8 10
12 14 - 24
V
Type
- - - - - - - - +COM
Terminal
No.
2 4 6 8 10
12
14 16 18
20
Output
No. 1 3 5 7 9 11
13 15 - 24
V
Type
- - - - - - - - +COM
•
EX510-S102
Terminal No.
1 3 5 7 9 11
13 15 17
19
Output
No. 0 2 4 6 8 10
12 14 - 0
V
Type
+ + + + + + + + -COM
Terminal
No.
2 4 6 8 10
12
14 16 18
20
Output
No. 1 3 5 7 9 11
13 15 - 0
V
Type
+ + + + + + + + -COM
∗
: Only a flat cable type manifold (P kit) can be connected to EX510-S 02 .
It cannot be connected to PCW type (G/J kit) according to the different pin assign.
•
Use of remaining output (Only for EX510-S 01 )
Remaining output of SI unit can be used by using a cable assembly for output.
(Refer to the figure below.)
Refer to "SI unit specifications" on page 31 for the load current restriction
of SI unit.
Power consumption of each valve series is shown in the table below.
Refer to the catalog of each valve series for detail.
Valve series
Power consumption
SY3000/5000/7000/9000
Standard: 0.4 W (approx. 17 mA)
With power saving circuit: 0.1 W (approx. 4 mA)
SYJ3000/5000/7000
Standard: 0.4 W (approx. 17 mA)
With power saving circuit: 0.1 W (approx. 4 mA)
VQZ1000/2000/3000
Standard: 1.0 W (approx. 42 mA)
Low wattage: 0.5 W (approx. 21 mA)
Refer to "Wiring of the branch cable and connector for connecting
load" on page 29 for how to wire the cable assembly for output.
NOTE
Do not pull the cable assembly for output strongly. It can cause defective connection or
broken wire.