Wiring of the branch cable, and load electric wire and terminal block connector
•
Insert flat blade watch driver from slots on a
terminal block connector to the end position.
•
Hold clamping part opened with a blade of the
driver.
•
Insert electric wire into a clamping unit of a
terminal block and pull the driver to finish wiring.
•
Applicable electric wire size is 0.08 to 1.5 mm
2
(AWG 16 to 28).
•
Wire sheath stripped length is 5 to 6 mm.
•
Too long stripped length might expose
conductor and cause insulation failure, and too
short stropped length might get the sheath
caught or make the conductor unclamped or
clamped improperly resulting in contact failure
or disconnection of electric wire.
•
The flat blade watch driver shall have
2.5 mm x 0.4 mm blade end width and hold the
clamp opened.
∗
: For crimping of a branch connector, refer to page 17.
The terminal block connector can be connected with the following electric wires.
•
Solid wire, fine stranded wire, stranded conductor ultrasonically bonded, stranded conductor with ferrule,
stranded conductor with pin terminal.
Wiring of power supply line and terminal block for external power supply.
•
Applicable electric wire size is 0.14 to 1.5 mm
2
(AWG 16 to 26).
•
Wire sheath stripped length is 4 to 6 mm.
•
Too long stripped length might expose conductor and cause insulation failure, and too short stripped
length might get the sheath caught or make the conductor unclamped or clamped improperly resulting in
contact failure or disconnection of electric wire.
•
The flat blade watch driver shall have 2.5 mm x 0.4 mm blade end width and hold the clamp opened.
•
Tightening torque for terminal block: 0.22 Nm at minimum.
Maximum load current
Internal power supply type (EX510-DYN3, DYP3)
•
The following three requirements shall be satisfied: (1) 0.5 A or less per point.
(2) 1 A or less per unit.
(3) Total current from OUT0 to 7 and from OUT8 to
15 is 1 A respectively.
Auxiliary power supply type (EX510-DYN4, DYP4)
•
The following three requirements shall be satisfied: (1) 0.5 A or less per point.
(2) 3 A or less per unit.
(3) Total current from OUT0 to 7 and from OUT8 to
15 is 1.5 A respectively.
For the load to the light, place an in-rush current restriction resistor to prevent potential fusing due to
in-rush current.