38-
10.
Troubleshooting
The following shows the troubleshooting related the SI Unit.
Table 10-1. Troubleshooting related COM LED indication
No.
Content
Probable causes
Checking methods and measures
1 COM LED is OFF.
Power supply for logic/input is low
(< approx. 16.8 VDC) or not
present.
Check the power supply voltage for
logic/input being supplied to the SI Unit.
Supply the voltage considering the voltage
drop on the wiring.
The communication/power cable
is broken.
Check the connection of the
communication/power cable.
2
COM LED is green ON.
The port LED of the
IO-Link master is green
flashing *.
The communication/power cable
is broken.
Check the connection of the
communication/power cable.
3
COM LED is green ON.
The port LED of the
IO-Link master is green
ON *.
The IO-Link master port is not in
IO-Link mode.
Set the IO-Link master port to IO-Link
mode.
Process data size of the IO-Link
master is smaller than the process
data size of the SI Unit.
Set the process data size of the IO-Link
master to be larger than the process data
size occupied by the SI Unit.
4
COM LED is green ON.
The port LED of the
IO-Link master is green
blinking fast *.
The IO-Link master has detected
a device matching error.
Disable the device matching function on
the IO-Link master or connect an SI Unit
that matches the DeviceID or
SerialNumber registered in the IO-Link
master.
Note
LED indicator status may vary depending upon the IO-Link master in use.
Check the specification of the IO-Link master for details.