background image

No.EX

※※

-OMU1012 

 

 

 

 

 

 

 
 

PRODUCT NAME

 

 

SI unit

 

for CC-Link IE Field 

 

MODEL / Series / Product Number

 

 

EX250-SCF1-X200 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for EX250-SCF1-X200

Page 1: ...No EX OMU1012 PRODUCT NAME SI unit for CC Link IE Field MODEL Series Product Number EX250 SCF1 X200...

Page 2: ...oduct elements 8 Mounting and Installation 9 Wiring 9 Setting 13 Maintenance 18 Troubleshooting 19 Specification 22 Specifications 22 Dimensions 24 Option 25 Refer to the operation manual EX250 IE1 IE...

Page 3: ...f equipment failure when configuring the equipment 2 Only personnel with appropriate training should operate machinery and equipment The product specified here may become unsafe if handled incorrectly...

Page 4: ...responsibility a replacement product or necessary parts will be provided This limited warranty applies only to our product independently and not to any other damage incurred due to the failure of the...

Page 5: ...rate in an atmosphere containing flammable or explosive gases Fire or an explosion can result This product is not designed to be explosion proof If using the product in an interlocking circuit Provide...

Page 6: ...IP67 protection cannot be guaranteed if the screws are not tightened to the specified torque Never mount a product in a location that will be used as a foothold The product may be damaged if excessive...

Page 7: ...exposed to vibration or impact Otherwise failure or malfunction can result Do not use the product in an environment that is exposed to temperature cycle Heat cycles other than ordinary changes in tem...

Page 8: ...nt communicate through the SI unit Up to 32 inputs can be connected to the SI unit using Input blocks Up to 32 outputs from combined EX9 Output blocks and valve manifolds can be connected to the SI un...

Page 9: ...PORT2 P2 3 Power supply connector Supplies power to the solenoid valve the output block SI unit and the input block 1 4 Input block connector Connects the input block 5 Output block connector Connects...

Page 10: ...er supply pay attention to the range of each supply voltage Power for sensor is supplied to sensor connected with input block Select sensor concerning voltage drop up to maximum 1 V inside the unit at...

Page 11: ...10 No EX OMU1012 Ground terminal Connect the ground terminal to ground Resistance to ground should be 100 ohms or less...

Page 12: ...sent and received Example of the cable with connector NBC MSX 1 0 94F SCO Order No 1407467 1 m NBC MSX 2 0 94F SCO Order No 1407468 2 m NBC MSX 5 0 94F SCO Order No 1407469 5 m etc PHOENIX CONTACT Pow...

Page 13: ...lve unit Replace the SI unit There is no need to remove the tie rod Re mount the input block and end plate that was removed and tighten the screws to the specified tightening torque 0 6 Nm Precautions...

Page 14: ...trol and input Flickering Unit test mode Test mode ON Test normal mode end RUN Green ON Operating normally OFF Node alarm occurs D LINK Green ON Cyclic transmission being performed OFF Cyclic transmis...

Page 15: ...to C x1 0 to 9 The station number should be set within the range of 01 to C0 120 If the number is set to 00 or to C1 121 or above the ERR LED will turn on Turn the power off and correct the setting ER...

Page 16: ...mory map and diagnostic information 1 Occupation point of device parameter Device type Device name Occupation size Remote input RX 32 points Remote output RY 32 points Remote register RWw 4 words Remo...

Page 17: ...ere RWw1 Unused RWr2 Error diagnostics moderate RWw2 Unused RWr3 Error diagnostics light RWw3 Unused Diagnostics information details Register BitNo Description RWr0 0 Reserved 9 10 Error generation st...

Page 18: ...alve is mounted on the standard wiring manifold the output number for the B side valve is skipped Custom wiring for mixed mounting single solenoid valves and double solenoid valves can be specified wi...

Page 19: ...the cable See the specification of a cable to be used for the conductive resistance SI unit No error in operation and display If any error is found in the operation or on the display replace the unit...

Page 20: ...LED is OFF SI unit RUN LED is OFF SI unit D LINK LED is OFF Refer to fault No 2 Refer to fault No 4 Refer to fault No 5 SI unit P1 P2 LINK LED is OFF Refer to fault No 3 Yes No Only the output of the...

Page 21: ...the power supply cable Solenoid valve power supply failure Check proper supply voltage of solenoid valve power supply Supply 24 VDC 10 5 to the solenoid valve power supply Fault No 3 Problem Possible...

Page 22: ...d SY SV SO700 series 32 points VQC series 24 points Change the number of solenoids to within the specification Fault No 7 Problem Possible cause Investigation method Countermeasures Solenoid valves do...

Page 23: ...ote device station Baud rate 1 Gbps Station number assignment range 1 to 120 Network number assignment range 1 to 239 Configuration file CSP Power supply voltage Power supply for control and input blo...

Page 24: ...age load EX9 OEP1 M12 connector 2 outputs source PNP negative common high wattage load EX9 PE1 2 M12 connector power block 2 Applicable output component to one station on U side Part number Remarks EX...

Page 25: ...24 No EX OMU1012 Dimensions...

Page 26: ...Power supply cable Cable outer diameter 6 4 Wire gauge 0 3 mm2 AWG22 Wire outer diameter 1 65 mm Minimum bending radius 40 mm Fixed 2 End plate Input block side EX250 EA1 EX250 EA2 3 End Plate R Outp...

Page 27: ...block Output block and Power block Proper use of this waterproof cap can achieve IP67 enclosure The waterproof caps are delivered together with the Power block as accessories Note Tighten the waterpr...

Page 28: ...hiyoda ku Tokyo 101 0021 JAPAN Tel 81 3 5207 8249 Fax 81 3 5298 5362 URL http www smcworld com Note Specifications are subject to change without prior notice and any obligation on the part of the manu...