background image

 

-6- 

 

No.EX

※※

-OMU1012 

 

 

Environment 

•Select the proper type of protection according to the environment of operation. 

IP67 protection is achieved when the following conditions are met. 

(1) The units are connected properly with fieldbus cable with M12 connector and power cable with M12/M8 

connector. 

(2) Suitable mounting of each unit and manifold valve. 

If using in an environment that is exposed to water splashes, please take measures such as using a cover. 

•Do not use in a place where the product could be splashed by oil or chemicals. 

If the product is to be used in an environment containing oils or chemicals such as coolant or cleaning solvent, even 
for a short time, it may be adversely affected (damage, malfunction etc.). 

•Do not use the product in an environment where corrosive gases or fluids could be splashed. 

Otherwise damage to the product and malfunction can result. 

•Do not use in an area where surges are generated. 

If there is equipment which generates a large amount of surge (solenoid type lifter, high frequency induction 
furnace, motor, etc.) close to the SI unit, this may cause deterioration or breakage of the internal circuit of the SI 
unit. Avoid sources of surge generation and crossed lines. 

•When a surge-generating load such as a relay or solenoid is driven directly, use an SI unit with a built-in 

surge absorbing element. 

Direct drive of a load generating surge voltage can damage the SI unit. 

•The product is CE marked, but not immune to lightning strikes. Take measures against lightning strikes 

in the system. 

•Prevent foreign matter such as remnant of wires from entering the SI unit to avoid failure and 

malfunction. 

Otherwise failure or malfunction can result. 

•Mount the product in a place that is not exposed to vibration or impact. 

Otherwise failure or malfunction can result. 

•Do not use the product in an environment that is exposed to temperature cycle. 

Heat cycles other than ordinary changes in temperature can adversely affect the inside of the product. 

•Do not expose the product to direct sunlight. 

If using in a location directly exposed to sunlight, shade the product from the sunlight. 
Otherwise failure or malfunction can result. 

•Keep within the specified ambient temperature range. 

Otherwise malfunction can result. 

•Do not operate close to a heat source, or in a location exposed to radiant heat. 

Otherwise malfunction can result.

 

 

Adjustment and Operation 

•Set the switches by using a sharp-pointed screwdriver etc. 

It may damage set switches. 

•Perform settings suitable for the operating conditions. 

Incorrect setting can cause operation failure. 
For details of each setting, refer to page 

14

 of this manual. 

•Please refer to the PLC manufacturer's manual etc. for details of programming and addresses. 

For the PLC protocol and programming refer to the relevant manufacturer's documentation. 

 

Maintenance 

•Turn off the power supply, stop the supplied air, exhaust the residual pressure and verify the release of 

air before performing maintenance. 

There is a risk of unexpected malfunction. 

•Perform regular maintenance and inspections. 

There is a risk of unexpected malfunction. 

•After maintenance is complete, perform appropriate functional inspections. 

Stop operation if the equipment does not function properly. 
Otherwise safety is not assured due to an unexpected malfunction or incorrect operation. 

•Do not use solvents such as benzene, thinner etc. to clean the each unit. 

They could damage the surface of the body and erase the markings on the body. 
Use a soft cloth to remove stains. 
For heavy stains, use a cloth soaked with diluted neutral detergent and fully squeezed, then wipe up the stains 
again with a dry cloth. 

Summary of Contents for EX250-SCF1-X200

Page 1: ...No EX OMU1012 PRODUCT NAME SI unit for CC Link IE Field MODEL Series Product Number EX250 SCF1 X200...

Page 2: ...oduct elements 8 Mounting and Installation 9 Wiring 9 Setting 13 Maintenance 18 Troubleshooting 19 Specification 22 Specifications 22 Dimensions 24 Option 25 Refer to the operation manual EX250 IE1 IE...

Page 3: ...f equipment failure when configuring the equipment 2 Only personnel with appropriate training should operate machinery and equipment The product specified here may become unsafe if handled incorrectly...

Page 4: ...responsibility a replacement product or necessary parts will be provided This limited warranty applies only to our product independently and not to any other damage incurred due to the failure of the...

Page 5: ...rate in an atmosphere containing flammable or explosive gases Fire or an explosion can result This product is not designed to be explosion proof If using the product in an interlocking circuit Provide...

Page 6: ...IP67 protection cannot be guaranteed if the screws are not tightened to the specified torque Never mount a product in a location that will be used as a foothold The product may be damaged if excessive...

Page 7: ...exposed to vibration or impact Otherwise failure or malfunction can result Do not use the product in an environment that is exposed to temperature cycle Heat cycles other than ordinary changes in tem...

Page 8: ...nt communicate through the SI unit Up to 32 inputs can be connected to the SI unit using Input blocks Up to 32 outputs from combined EX9 Output blocks and valve manifolds can be connected to the SI un...

Page 9: ...PORT2 P2 3 Power supply connector Supplies power to the solenoid valve the output block SI unit and the input block 1 4 Input block connector Connects the input block 5 Output block connector Connects...

Page 10: ...er supply pay attention to the range of each supply voltage Power for sensor is supplied to sensor connected with input block Select sensor concerning voltage drop up to maximum 1 V inside the unit at...

Page 11: ...10 No EX OMU1012 Ground terminal Connect the ground terminal to ground Resistance to ground should be 100 ohms or less...

Page 12: ...sent and received Example of the cable with connector NBC MSX 1 0 94F SCO Order No 1407467 1 m NBC MSX 2 0 94F SCO Order No 1407468 2 m NBC MSX 5 0 94F SCO Order No 1407469 5 m etc PHOENIX CONTACT Pow...

Page 13: ...lve unit Replace the SI unit There is no need to remove the tie rod Re mount the input block and end plate that was removed and tighten the screws to the specified tightening torque 0 6 Nm Precautions...

Page 14: ...trol and input Flickering Unit test mode Test mode ON Test normal mode end RUN Green ON Operating normally OFF Node alarm occurs D LINK Green ON Cyclic transmission being performed OFF Cyclic transmis...

Page 15: ...to C x1 0 to 9 The station number should be set within the range of 01 to C0 120 If the number is set to 00 or to C1 121 or above the ERR LED will turn on Turn the power off and correct the setting ER...

Page 16: ...mory map and diagnostic information 1 Occupation point of device parameter Device type Device name Occupation size Remote input RX 32 points Remote output RY 32 points Remote register RWw 4 words Remo...

Page 17: ...ere RWw1 Unused RWr2 Error diagnostics moderate RWw2 Unused RWr3 Error diagnostics light RWw3 Unused Diagnostics information details Register BitNo Description RWr0 0 Reserved 9 10 Error generation st...

Page 18: ...alve is mounted on the standard wiring manifold the output number for the B side valve is skipped Custom wiring for mixed mounting single solenoid valves and double solenoid valves can be specified wi...

Page 19: ...the cable See the specification of a cable to be used for the conductive resistance SI unit No error in operation and display If any error is found in the operation or on the display replace the unit...

Page 20: ...LED is OFF SI unit RUN LED is OFF SI unit D LINK LED is OFF Refer to fault No 2 Refer to fault No 4 Refer to fault No 5 SI unit P1 P2 LINK LED is OFF Refer to fault No 3 Yes No Only the output of the...

Page 21: ...the power supply cable Solenoid valve power supply failure Check proper supply voltage of solenoid valve power supply Supply 24 VDC 10 5 to the solenoid valve power supply Fault No 3 Problem Possible...

Page 22: ...d SY SV SO700 series 32 points VQC series 24 points Change the number of solenoids to within the specification Fault No 7 Problem Possible cause Investigation method Countermeasures Solenoid valves do...

Page 23: ...ote device station Baud rate 1 Gbps Station number assignment range 1 to 120 Network number assignment range 1 to 239 Configuration file CSP Power supply voltage Power supply for control and input blo...

Page 24: ...age load EX9 OEP1 M12 connector 2 outputs source PNP negative common high wattage load EX9 PE1 2 M12 connector power block 2 Applicable output component to one station on U side Part number Remarks EX...

Page 25: ...24 No EX OMU1012 Dimensions...

Page 26: ...Power supply cable Cable outer diameter 6 4 Wire gauge 0 3 mm2 AWG22 Wire outer diameter 1 65 mm Minimum bending radius 40 mm Fixed 2 End plate Input block side EX250 EA1 EX250 EA2 3 End Plate R Outp...

Page 27: ...block Output block and Power block Proper use of this waterproof cap can achieve IP67 enclosure The waterproof caps are delivered together with the Power block as accessories Note Tighten the waterpr...

Page 28: ...hiyoda ku Tokyo 101 0021 JAPAN Tel 81 3 5207 8249 Fax 81 3 5298 5362 URL http www smcworld com Note Specifications are subject to change without prior notice and any obligation on the part of the manu...

Reviews: