Installation & Maintenance Manual

Fieldbus system - SI unit

Type EX180 Series for DeviceNet

TM

EX180-SDN3 /SDN4 /SDN5 /SDN6

Fieldbus interface
connector (BUS)

Item

Description

The connector for the DeviceNet

TM

bus line

(

).

6

Power supply
connector (PWR(V))

The connector for the power supply (

)

used to supply the power for the solenoid
valves.

7

FG terminal

Functional Earth.

PW

R(V

)

PW

R

MN

S

4

3 2

5

1

1

No.

2

3

Do not disassemble, modify (including changing the printed
circuit board) or repair.

An injury or failure can result.

Do not operate the product outside of the specifications.

Do not use for flammable or harmful fluids.
Fire, malfunction, or damage to the product can result.
Verify the specifications before use.

Do not operate in an atmosphere containing flammable or
explosive gases.

Fire or an explosion can result.
This product is not designed to be explosion proof.

If using the product in an interlocking circuit:

•Provide a double interlocking system, for example a mechanical

system.

•Check the product regularly for proper operation.
Otherwise malfunction can result, causing an accident.

The following instructions must be followed during maintenance:

•Turn off the power supply.
•Stop the air supply, exhaust the residual pressure and verify that the

air is released before performing maintenance.

Otherwise an injury can result.

Safety Instructions

These safety instructions are intended to prevent hazardous situations
and/or equipment damage.
These instructions indicate the level of potential hazard with the labels of
"Caution", "Warning" or "Danger". They are all important notes for safety
and must be followed in addition to International standards (ISO/IEC)
and other safety regulations.

Warning

CAUTION indicates a hazard with a low level of risk
which, if not avoided, could result in minor or
moderate injury.

Caution

Warning

Danger

WARNING indicates a hazard with a medium level
of risk which, if not avoided, could result in death or
serious injury.

DANGER indicates a hazard with a high level of risk
which, if not avoided, will result in death or serious
injury.

Summary of Product Parts

Installation

<EX180-SDN3 /SDN4 /SDN5 /SDN6 >

EX180-TFO09

This product is class A equipment that is intended for use in an industrial
environment.
There may be potential difficulties in ensuring electromagnetic
compatibility in other environments due to conducted as well as radiated
disturbances.

NOTE

When conformity to UL is necessary the SI unit must be used with a UL
1310 Class2 power supply.

Caution

After maintenance is complete, perform appropriate functional
inspections.

Stop operation if the equipment does not function properly.
Safety cannot be assured in the case of unexpected malfunction.

Provide grounding to assure the safety and noise resistance of
the Fieldbus system.

Individual grounding should be provided close to the product with a
short cable.

Display

LED diagnostic display.

Setting switches

Switches to set the MAC ID and
communication speed (inside the cover).

4

5

6

Communication connector for DeviceNet

TM

(1 pc.)

6

(EX180-CDN1)

(EX180-CDN2)

EX180-SDN3/4/5/6

EX180-SDN3A/4A/5A/6A

7

Power supply

connector (1 pcs.)

(EX180-CP1)

<Accessories>

General Instructions on Installation

Applicable valve series

The EX180 series SI unit can be mounted on the following valve
manifolds.
SJ2000/3000, S0700 series

: Refer to the catalogues and operation manuals for details of the solenoid

valves and manifolds.

How to mount the manifold
1. Mount the SI unit to the manifold so that the mounting guide of the

SI unit case mates with the manifold groove.

2. Secure the SI unit using the two sliding locks.

PW

R(V

)

PW

R

MN

S

PW

R(V

)

PW

R

MN

S

1

2

Wiring

1. Wiring for communication

Wiring of the DeviceNet

TM

communication cable and connector is

shown below.

(1)Connect the signal wires to the assigned pins. (Figure 1)

The required tightening torque is 0.5 to 0.6 Nm.

V+ CAN_H Drain CAN_L V-

White Drain Blue Black

Red

White Drain Blue Black

Red

V+ CAN_H Drain CAN_L V-

Installation  (Continued)

Figure 1

(2)A bus termination is required at both ends of the DeviceNet

TM

bus

segment as shown in Figure 2.
The specification of the terminating resistor is 121 Ω ±1%, 1/4 W.

V+ CAN_H Drain CAN_L V-

Terminating resistor

White Drain

Blue Black

Red

White Drain Blue Black

Red

V+ CAN_H Drain CAN_L V-

Terminating resistor

Figure 2

(3)How to connect.

PW

R(V

)

PW

R

MN

S

Communication connector

for DeviceNet

TM

Figure 3

2. Wiring of the power supply

Connect the power supply to the power supply connector (1 pc.).
The EX180 power supply structure consists of two supplies.
These supplies can be operated using a single or dual power supply
system.
Connect the wires to the assigned pins. (Figure 4, Figure 5)
The required tightening torque is 0.22 to 0.25 Nm.

•Note

Connect the FG terminal to ground with a ground resistance of
100 Ω or less.

DeviceNet

TM 

power supply 

24 VDC

Solenoid valve

power supply

24 VDC

24 VDC

Figure 4

A. Dual power supplies

B. Single power supply

PW

R(V

)

PW

R

MN

S

Power supply connector

Figure 5