Operation
8-12
06/18/04
8.6.2 Setting mode, Level 2
1.Fine Control of Internal Sensor
Setting range : -9.99 to 9.99deg.C
Min. increment : 0.01deg.C
Indicated content : Fine adjusting value for internal temp.
Sensor(Ex. : -0.07deg.C)
Function : Sets the fine adjusting value to calibrate the
internal temp. sensor. If 0.07deg.C is set in
this item, the reading of temp. sensor is
higher by 0.07deg.C and actually, the temp.
is controlled to lower one by 0.07deg.C.
2.Fine Control of External Sensor
Setting range : -9.99 to 9.99deg.C
Min. increment : 0.01deg.C
Indicated content : Fine adjustment value for external
temp. sensor(Ex. : 0.05deg.C)
Function : Sets the fine adjusting value to calibrate the
external temp. sensor if it is mounted
optionally. If 0.05deg.C is set in this item, the
reading of temp. sensor is higher by
0.05deg.C and actually, the temp. is
controlled to lower one by 0.05deg.C.
3.PB Range
Setting range : 0.3 to 9.9deg.C
Min. increment : 0.1deg.C
Indicated content : PB range(Ex. : 2.0deg.C)
Function : Sets PB range used for PID control.
4.ARW Range
Setting range : 0.3 to 9.9deg.C
Min. increment : 0.1deg.C
Indicated content : ARW range(Ex. : 2.2deg.C)
Function : Sets integral operation range of PID control.
THERMO-CON
F i n e C o n t r o l o f
I n t e r n a l S e n s o r
MO D E < - 0 . 0 7 ° C
THERMO-CON
P B R a n g e
MO D E < 2 . 0 ° C
THERMO-CON
A R
W
R a n g e
MO D E < 2 . 2 ° C
THERMO-CON
F i n e C o n t r o l o f
E x t e r n a l S e n s o r
MO D E < 0 . 0 5 ° C