2
Programming
This product has three Model Modes of operations:
Model Mode 1 = Standard Mode
Model Mode 2 = Tecma Silence (Series)
Model Mode 3 = Tecma Prestige (Series)
Model Mode 4 = European Mode
This product has been factory default set to Model Mode 2
(see page 4)
Factory Default: T1 = 20 seconds Model
Mode
= Tecma Silence (Series)
Please Note:
If you have a Tecma Silent (Series)
Toilet System
ALWAYS
choose Model
Mode 2
.
Should you wish to change these settings then proceed as below.
Advisory Warning:
1.5 litres per flush is the recommended minimum flush setting for
discharge lines of less than 6 feet. Dilution is the secret to efficient waste transfer,
through pipes and must be considered when programming your controller. Increase your
flush volume appropriately if the discharge line is greater than 6 feet in length.
Note
– Variations in controllers may substitute the following buttons: Flush =
Normal Flush, Fill = Water Only, Empty = Empty Only.
Programmable Time Options
(Actuate to
0.1%)
Timer T1 & T2 (
Water
Valve/Pump) & (Extraction Motor) from 1 to 20 seconds.
Timer T3 (
Water
Valve/Pump) is programmable from 0 to 20 seconds.
This manual applies to units manufactured after 01/08/2012