background image

 Drive Startup Manual DSD412  
 

 

Page 10 

© 2020 Smartrise Engineering, Inc. All Rights Reserved  

March 5, 2020 

Parameter 

Description 

Recommended Value 

Additional Information 

11 

Motor RPM 

Motor Name Plate 

 

17 

Rated Car Speed 

Per Job Specification 

 

49 

Weak Field Current 

Motor Name Plate 

If this value is greater than the 

rated field current, then the field 

will never weaken. 

50 

Rated Field Current 

Motor Name Plate 

The drive must be configured for 

the correct field current range. 

See the 

Magnetek DSD 412

 

Manual for DIP switch settings. 

52 

Rated Field Voltage 

Motor Name Plate 

 

53 

Standby Field Current 

25% 

This parameter cannot be set to 

ON until performing the self-

tune. 

Magnetek DSD412 Drive Self-Tune Procedure

 

Perform the Magnetek DSD412 drive self-tune procedure as follows. 

 

Place a jumper from LPR on the DIN rail to SAFE. 

 

Put the NVRAM Protected switch in the Not Protected position. 

 

Perform PCU DIAGNOSTICS Function 998 to verify armature and field circuitry.  

 

Perform SELF-TUNE PARAMETER TEST Function # 997. The drive should display PASS 

after a few seconds. Set Parameter #2 to ON. 

 

Remove the jumper and perform Function #994 to permanently save the changed 

values. 

 

Verify the Smartrise MR board LCD is not showing an active fault as indicated by a 

flashing Red LED, and it displays Construction Mode. 

 

Close the Run Bug Stop switch. 

 

Command the Car to move. 

 

Verify the brake is picking/holding after a valid run command is given.  

 

Verify the brake is dropping once the command is removed. 

 

Verify the timing and operation of the brake to ensure the motor is not running through 

the brake prior to it picking. 

 

Is the brake inoperative? 
a.

 

If the brake is operative, go to step 13. 

b.

 

If the brake is inoperative, check the following: 

 

Check for DC voltage between points K1 and K2 on the Machine Room DIN rail. 

 

Verify this voltage is also at the brake coil when commanded to pick. 

 

Ensure this voltage corresponds to the voltage the brake coil is rated for. 

 

If problems persist, contact Smartrise for assistance.  

 

The encoder feedback may be out of phase upon first power-up. This may cause the 

motor to run faster than commanded and/or give drive fault 408/98. Is the encoder 

feedback out of phase? 

Summary of Contents for DSD412

Page 1: ......

Page 2: ...Page intentionally left blank...

Page 3: ...History Date Version Summary of Changes October 23 2018 1 0 Initial Submittal August 23 2019 2 0 Changed cover page New document format Added secondary brake wiring December 12 2019 3 0 Updated Accuco...

Page 4: ...Drive Startup Manual DSD412 Page ii 2020 Smartrise Engineering Inc All Rights Reserved March 5 2020 Page intentionally left blank...

Page 5: ...otor Encoder 3 Construction 4 Powering Up 6 Setup 6 Drive Power Up Sequence 7 Abnormal Display Conditions 8 Fan Check 9 Verify Parameters 9 Magnetek DSD412 Drive Self Tune Procedure 10 Shuddering at H...

Page 6: ...ures Figure 1 DSD412 Drive 1 Figure 2 Example of Parameter Table 1 Figure 3 Ground Bus Terminal 2 Figure 4 Example of Construction Wiring 5 Figure 5 Breakers 6 Figure 6 Terminal Connections 6 Figure 7...

Page 7: ...12 March 5 2020 2020 Smartrise Engineering Inc All Rights Reserved Page v List of Tables Table 1 Wiring References for Common Encoders 3 Table 2 Abnormal Display Conditions and Solutions 8 Table 3 Mag...

Page 8: ...Drive Startup Manual DSD412 Page vi 2020 Smartrise Engineering Inc All Rights Reserved March 5 2020 Page intentionally left blank...

Page 9: ...D412 Drive The DSD412 drive is a DC drive Figure 1 DSD412 Drive Equipment Settings Verification Set and verify the equipment matches the job specific parameters for proper operation See the C4 Control...

Page 10: ...g rod in the pit The controller has a common ground bus terminal connection Figure 3 Ground Bus Terminal The building motor transformer and filter s must all share a common ground This removes ground...

Page 11: ...the motor and encoder cable See the C4 Controller sheet 04 Drive and Motor for job specific information Connect motor leads to the M contactor at T1 T2 T3 Connect the encoder cable to the TB1 encoder...

Page 12: ...and LFB a If rear doors are used connect LRT LRM and LRB Connect a jumper from H120 to PIT BUF BFL and TFL If secondary brake is present connect M120 to SFM Connect H120 through your machine room Run...

Page 13: ...Drive Startup Manual DSD412 March 5 2020 2020 Smartrise Engineering Inc All Rights Reserved Page 5 Figure 4 Example of Construction Wiring...

Page 14: ...ct Close the two pole breaker and all pushbutton breakers Verify the LCD on the Smartrise board and the Magnetek Drive powers up Figure 5 Breakers Setup Perform the following connections as shown in t...

Page 15: ...Figure 8 Encoder Connection Apply the control and three phase power Verify that the control power is between 103 VAC and 126 VAC Press the RESET push button on the front of the power cube and observe...

Page 16: ...ower is missing Measure and verify three phase power input at the drive terminals Check the three phase power fuses FAULT LED lights and a fault code appears on the SCDU Refer to the Fault Error Codes...

Page 17: ...r involved STORE PARAMETERS Function 994 so that power can be removed and reapplied without losing the entered parameters Set the NVRAM PROTECTION switch to the protect position UN PROT NV RAM light i...

Page 18: ...EST Function 997 The drive should display PASS after a few seconds Set Parameter 2 to ON Remove the jumper and perform Function 994 to permanently save the changed values Verify the Smartrise MR board...

Page 19: ...rmer secondary voltage be at a minimum equal to the rated armature VDC For best results that account for sagging utility etc VAC 1 05 x VDC is a better number to use Make sure that the motor weak fiel...

Page 20: ...lt for troubleshooting drive fault Proper Direction Make sure the car is moving in the same direction as the control switch on the Run Bug See Wrong Direction for troubleshooting proper direction faul...

Page 21: ...the terminal See the C4 Controller sheet 01 Getting Started for more information If the brake has the proper voltage check the following During a run command check the DC voltage between points K1 K2...

Page 22: ...Drive Startup Manual DSD412 Page 14 2020 Smartrise Engineering Inc All Rights Reserved March 5 2020 Appendix The figure below shows the terminal locations Figure 10 Terminal Locations...

Reviews: