SmartOne 70-600000-001 Installation Instructions Download Page 4

4

installation foR a 4-11/16 in. squaRe oR 4 in. squaRe 

electRical Box (see fiGuRe 3)

note:

  The depth of the box is to be determined per Article 370 of the National 

Electrical Code. RRM  volume is 8.94 cubic-inches. 

1. It is recommended that the module address be programmed prior to instal-

lation. Refer to the control unit manual for device address programming.

Using a handheld programmer to set the module address requires a 24 VDC

power supply (see Figure 2). A handheld programmer can only program the

module address. All other configurations can be set using with the control

panel or configuration software.

2. Make all wiring connections as shown in the wiring diagram (see Figure 2).

Ensure that all wiring is free of opens, shorts and ground faults. Verify that

all wires are insulated up to and touching the terminal block, and that each

terminal screw is tight. Connect the Earth-Ground to the green screw on the

mounting bracket.

3.  Mount  the module to the 4 in. square or 4-11/16 in. electrical box (use adapter

ring for the 4-11/16 in. electrical box) .

4. Using the 2 provided screws, mount the wall plate to the electrical box as

shown in Figure 3.

note

:   See Appendix E of the corresponding Control Unit’s Installation, Operation 

and Maintenance Manual  for routing guidelines for power- limited and 

non-power-limited wiring. Refer to the reference table on the last page 

for the part number of the applicable manual. 

6. The RRM is shipped from the factory as an assembled component and

is not field-serviceable.

7. For ease of wiring, especially with solid wire, an extension ring or deeper

box can be used.

8. For Power-Limited Circuits, use Type FPL, FPLR, or FPLP cable per

Article 760 of the National Electrical Code (NEC). The note located on

product label  “ALL OTHERS-POWER LIMITED”  must be  removed  if

connected to a non-power limited supply source.

9. For a list of power supplies, refer to Chapter 1 of the applicable Control

Unit’s Installation, Operation and Maintenance Manual. Refer to the

reference table on the last page for the part number of the applicable

manual.

10. For a list of compatible solenoids, refer to Appendix C of the applicable

Control Unit’s Installation, Operation and Maintenance Manual. Refer to

the reference table on the last page for the part number of the applicable

manual.

11. To configure the RRM, refer to the applicable Control Unit’s Configuration

Software User’s Guide. Refer to the reference table on the last page for

the part number of the applicable user’s guide.

note:

    Releasing devices are Control Unit- and Configuration Software-depen-

dent.

12.

the use of shielded wire is not allowed for the Release circuit, psu

trouble circuit and 24VDc power circuit, except for very short

runs.

 The maximum amount of shielded wire which can be spliced into

or used on the referenced circuits is a combined total of 50 feet. When

multiple Remote Release Modules,  Addressable Signal Modules, and

Addressable Input Modules attached to the same SLC loop are using

shielded wire on their initiating circuits, remote LED circuits, 24V power

circuits, auxiliary circuits, notification appliance circuits or release circuits,

the total combined shielded wire on all of these circuits (not including the

SLC itself) must not exceed 200 feet. Refer to the control unit Installation,

Operation and Maintenance Manual for SLC loop wiring requirements.

supeRVision

Each Circuit is supervised for short circuit (only when using inline device  

06-220023-001 for solenoids), open circuit, and ground faults in order to be listed 

as power limited. Initiators are an exception; they are not supervised for short 

circuits, and are not listed as Non-Power Limited.

5

AP

PR

OVE

D

FM

Figure 3. Mounting the RRM in an Electrical Box

installation foR an in-caBinet RRM enclosuRe  

(see fiGuRe 4)

The RRM module is intended for mounting inside a suitable UL-864 Listed enclo-

sure with no other electronics. Use the mounting hardware (standoffs and screws) 

provided with the module. Provide a minimum 1/2 in. of clearance between the 

RRM(s) and enclosure (See Figure 4).

It is recommended that the module address be programmed prior to installation.  

Refer to the control panel manual for device address programming. Using a hand-

held programmer to set the module address requires a 24 VDC power supply (see 

Figure 2).  A handheld programmer can only program the module address.  All 

other configurations can be set using the control panel or configuration software.

Reviews: