GeneRal notes

1. Terminal connection supports wiring from #18 AWG (1.0 mm

2

) to #12

AWG (4.0 mm

2

). Wire sizes determine electrical box depth.

2. Refer to applicable Control Panel Manual for addressable loop wiring

specification.

3. SLC Line wiring is power-limited and supervised.
4. Do not attach power-limited and non-power-limited wiring to the same

terminal block.

5. Route non-power-limited wires at least 1/4 in. away from all power- 

limited wiring.

WiRinG DiaGRaM

Figure 2. RRM Wiring

6

AP

PR

OV

ED

FM

APPR

OVED

FM

APP

RO

VE

D

FM

STANDOFFS

INSULATOR

2. Using the template in Figure 5, mark the mounting holes in the

cabinet that the RRM is going to be installed.

3. Drill the mounting holes in the enclosure.
4. Install provided standoffs in the cabinet mounting holes.
5. Mount the cabinet.
6. Run the necessary wiring and conduit to the cabinet.

note

: See Appendix E of the corresponding Control Unit’s Installa-

tion, Operation and Maintenance Manual for routing guidelines for

power-limited and non-power-limited wiring. Refer to the reference

table on the last page for the part number of the applicable manual.

7. Remove the insulator from the RRM.
8. On the RRM, loosen the mounting screws until each screw is flush

with the back of the module.

9. Place the RRM over the standoffs in the enclosure. Secure the

mounting screws to the standoffs.

10.  Make  all  wiring  connections  as  shown  in  the  wiring  diagram.             

Ensure that all wiring is free of opens, shorts and ground faults.

Verify that all wires are insulated up to and touching the terminal

block, and that each terminal screw is tight.

11. Replace the insulator on the RRM.

Figure 4. Minimum RRM Clearance and  

Mounting the RRM in a UL Listed Enclosure  

WARNING

!

ensure that all releasing devices are physically disconnected from 

the releasing circuits before performing any testing or maintenance.

RRM

½ in. (13 mm)

½ in.
(13 mm)

UL LISTED ENCLOSURE

S

S

S

S

S

P

P

P

P

REMOTE RELEASE MODULE (RRM)

TB2

TB3

TB1

4.7k EOL

Control Unit

SLC (TB1)

24 VDC

Release

+

+ +

-

+ -

PSU

STATUS

2

1

3 4 5

6

-

-

TB1

TB1

TB1

Or

DUAL-SOLENOID CIRCUIT

SINGLE-SOLENOID CIRCUIT

To next loop device

Blk

Red

Blk

Red

Blk

Red

Current Limiting Resistor

Other Assemblies

See the applicable Control Unit’s
Installation, Operation and
Maintenance Manual for a list of other
compatible releasing devices and
device-specific wiring instructions.

In-Line Releasing Device,
P/N 06-220023-001 (Must be close
nippled to solenoid enclosures)

In-Line Releasing Device, P/N 06-220023-001
(Must be close nippled to solenoid enclosures)

(Non-Power-Limited when an In-Line Releasing

Device not used) See General Note 4.

(W

ircuit is non-power-limited and not supervised

for shorts.)

hen an In-Line Releasing Device is not used, the

c

Supervised for open circuits and ground
faults.

OTHER COMPATIBLE
RELEASING DEVICES

A

A

B

B

1 2

3 4

SLC

2

1

3 4

To PSU dry contact trouble relay

(Trouble = contacts closed)

Legend:

Supervised

Power Limited

For a list of all compatible
releasing devices, refer to
Appendix C of the corresponding
Control Unit’s Installation, Operation
and Maintenance Manual.

Release Circuit:

Voltage:

Current:

24 VDC (nom.)

2.4 A (max.)

Or

2

1

3 4

2

1

3 4

2

1

3 4

Max. Current under Fault Conditions: 5A

To Earth Ground
(screw on mounting
bracket)

For a list of all compatible
power supplies, refer to
Chapter 1 of the corresponding
Control Unit’s Installation, Operation
and Maintenance Manual.