GeneRal notes
1. Terminal connection supports wiring from #18 AWG (1.0 mm
2
) to #12
AWG (4.0 mm
2
). Wire sizes determine electrical box depth.
2. Refer to applicable Control Panel Manual for addressable loop wiring
specification.
3. SLC Line wiring is power-limited and supervised.
4. Do not attach power-limited and non-power-limited wiring to the same
terminal block.
5. Route non-power-limited wires at least 1/4 in. away from all power-
limited wiring.
WiRinG DiaGRaM
Figure 2. RRM Wiring
6
AP
PR
OV
ED
FM
APPR
OVED
FM
APP
RO
VE
D
FM
STANDOFFS
INSULATOR
2. Using the template in Figure 5, mark the mounting holes in the
cabinet that the RRM is going to be installed.
3. Drill the mounting holes in the enclosure.
4. Install provided standoffs in the cabinet mounting holes.
5. Mount the cabinet.
6. Run the necessary wiring and conduit to the cabinet.
note
: See Appendix E of the corresponding Control Unit’s Installa-
tion, Operation and Maintenance Manual for routing guidelines for
power-limited and non-power-limited wiring. Refer to the reference
table on the last page for the part number of the applicable manual.
7. Remove the insulator from the RRM.
8. On the RRM, loosen the mounting screws until each screw is flush
with the back of the module.
9. Place the RRM over the standoffs in the enclosure. Secure the
mounting screws to the standoffs.
10. Make all wiring connections as shown in the wiring diagram.
Ensure that all wiring is free of opens, shorts and ground faults.
Verify that all wires are insulated up to and touching the terminal
block, and that each terminal screw is tight.
11. Replace the insulator on the RRM.
Figure 4. Minimum RRM Clearance and
Mounting the RRM in a UL Listed Enclosure
WARNING
!
ensure that all releasing devices are physically disconnected from
the releasing circuits before performing any testing or maintenance.
RRM
½ in. (13 mm)
½ in.
(13 mm)
UL LISTED ENCLOSURE
S
S
S
S
S
P
P
P
P
REMOTE RELEASE MODULE (RRM)
TB2
TB3
TB1
4.7k EOL
Control Unit
SLC (TB1)
24 VDC
Release
+
+ +
-
+ -
PSU
STATUS
2
1
3 4 5
6
-
-
TB1
TB1
TB1
Or
DUAL-SOLENOID CIRCUIT
SINGLE-SOLENOID CIRCUIT
To next loop device
Blk
Red
Blk
Red
Blk
Red
Current Limiting Resistor
Other Assemblies
See the applicable Control Unit’s
Installation, Operation and
Maintenance Manual for a list of other
compatible releasing devices and
device-specific wiring instructions.
In-Line Releasing Device,
P/N 06-220023-001 (Must be close
nippled to solenoid enclosures)
In-Line Releasing Device, P/N 06-220023-001
(Must be close nippled to solenoid enclosures)
(Non-Power-Limited when an In-Line Releasing
Device not used) See General Note 4.
(W
ircuit is non-power-limited and not supervised
for shorts.)
hen an In-Line Releasing Device is not used, the
c
Supervised for open circuits and ground
faults.
OTHER COMPATIBLE
RELEASING DEVICES
A
A
B
B
1 2
3 4
SLC
2
1
3 4
To PSU dry contact trouble relay
(Trouble = contacts closed)
Legend:
Supervised
Power Limited
For a list of all compatible
releasing devices, refer to
Appendix C of the corresponding
Control Unit’s Installation, Operation
and Maintenance Manual.
Release Circuit:
Voltage:
Current:
24 VDC (nom.)
2.4 A (max.)
Or
2
1
3 4
2
1
3 4
2
1
3 4
Max. Current under Fault Conditions: 5A
To Earth Ground
(screw on mounting
bracket)
For a list of all compatible
power supplies, refer to
Chapter 1 of the corresponding
Control Unit’s Installation, Operation
and Maintenance Manual.