2
7
3.00 in.
0.01 in.
1.80 in.
0.01 in.
Figure 5. RRM Mounting Template
oRDeRinG infoRMation
Description
part number
Remote Releasing Module
(With Standard Bracket and Front Cover Plate)
70-600000-001
Remote Releasing Module
(With In-Cabinet Bracket and Mounting Hardware)
70-600000-002
Inline Releasing Device (One Required For Each Solenoid
Release Circuit to be Supervised and Power Limited)
06-220023-001
End of Line Resistor, 4.7 K, 0.5 W
06-129025-006
specifications
WiRe stRippinG
Strip 1/4 in. from the ends of all wires that connect to the terminal block of the
module.
1/4 in.(6.4mm)
Figure 1. Wire Stripping
Single-Loop Panel Activation *
Up to 4 groups of 16 RRMs activated
simultaneously
Multi-Loop Panel Activation *
Up to 7 groups of 20 RRMs activated
simultaneously
* For further information on activation of RRMs, refer to the applicable
Installation, Operation and Maintenance manual and Configuration Software
User's Guide for your control unit.
Operating Voltage
24 VDC Nominal
Device Current (Remote Supply)
6.1 mA Standby
45 mA Alarm (Excluding Releasing
Devices)
Device Current (SLC)
410 µA Standby and Alarm
Operating Temperature Range
32ºF to 120ºF
(0ºC to 49ºC)
Operating Humidity Range
0% to 93% RH
Construction
High Impact Polymer Faceplate with a 16
gauge Aluminum Bracket
Shipping Weight
10.5 oz (298 g)
Compatible Electrical Boxes
North American 4-11/16 in. electrical box
with a double gang plaster ring (Rayco
Model 841 or equivalent)
4 in. square 2-1/8 in. deep box
Any suitable UL-864 Listed Enclosure
Releasing Circuit Output Current
2.4A Max. @ 24.0 VDC
Trouble Circuit Input
4.7K End of Line Resistor
"Open" contact = normal condition
SLC Wiring Configuration
• Class A,
• Class B,
• Class A, Style-7
Wiring
Unshielded
(See Note 12 for use of shielded wire)
note:
To ensure that all SLC-based output devices are activated within the
required time period, refer to the associated control unit’s Installation,
Operation and Maintenance manual.