Remote Releasing Module
DescRiption
The Remote Releasing Module (RRM) is a UL Listed, FM Approved
smartone
®
Field Device. The RRM provides the ability to remotely activate
extinguishing-system control devices. Connection is via the
smartone
com-
patible control panel’s Signaling Line Circuit (SLC). The module is field-pro-
grammable using the control panel keypad or Hand-Held Programmer.
The RRM provides internal supervision of communication with the control
unit, connections to external power supply, and memory status.
Solenoid release circuits are power-limited and supervised for short circuit
by using an In-line Releasing-Circuit Device (P/N 06-220023-001). In the
event of a ground fault, open, short or a relay contact failure, the device
will transmit a trouble status to the control unit.
A status LED is mounted on the RRM and indicates the module’s status:
Normal is indicated by a flash every 9 seconds; Output Activity is indicated
by the LED on continuously (no flashing); Trouble is indicated by the LED
being OFF.
The RRM is intended for indoor dry location use, and is available in two
models, one for mounting in a standard electrical box and a second model
for mounting in suitable UL-864 Listed cabinets.
p/n 70-600000-001: standard Mounting
•
North American 4-11/16 in. electrical box with a double gang plaster
ring (Rayco Model 841 or equivalent), 1/2 in. raised
•
4 in. square, 2-1/8 in. deep electrical box
p/n 70-600000-002: in-cabinet Mounting
•
Any suitable UL-864 Listed enclosure with no other electronics.
The module terminal block will accept #12, #14, #16 and #18 AWG wire
(4.0 mm
2
, 2.5 mm
2
, 1.5 mm
2
and
1.0 mm
2
respectively). Size #18 being a
minimum requirement. The use of solid wire is recommended.
TM
KIDDE-FENWAL INC.
400 MAIN STREET, ASHLAND, MA 01721
TEL: (508) 881-2000 FAX: (508) 881-8920
This literature is provided for informational purposes only.
KIDDE-FENWAL,INC. assumes no responsibility for the
product’s suitability for a particular application. The product
must be properly applied to work correctly.
If you need more information on this product, or if you have
a particular problem or question, contact KIDDE-FENWAL
INC., Ashland, MA 01721. Telephone: (508) 881-2000
06-236636-001 Rev. AD
©
2016 Kidde-Fenwal, Inc.
installation instRuctions
This device complies with Part 15 of the FCC rules. Operation is subject to the following two
conditions: (1) This device may not cause any harmful interference, and (2) This device must
accept any interference received, including interference that may cause undesired operation.
control unit
part number
installation,
operation and
Maintenance Manual
part number
configuration
software
user's Guide
part number
FenwalNET 6000:
74-600000-001
06-236529-001
06-236529-002
74-600000-510
06-236529-001
06-236529-002
ARIES:
76-600000-004
06-236530-001
06-236530-002
FenwalNET 8000-ML:
74-800100-001
06-237041-001
06-237042-001
74-800101-002
06-237041-001
06-237042-001
74-800200-001
06-237041-001
06-237042-001
74-800201-002
06-237041-001
06-237042-001
ARIES NET
Link
:
76-800100-001
06-237058-001
06-237059-001
76-800101-002
06-237058-001
06-237059-001
76-800200-001
06-237058-001
06-237059-001
76-800201-002
06-237058-001
06-237059-001
74-800102-001
06-237041-001
06-237042-001
74-800202-001
06-237041-001
06-237042-001
76-800102-001
06-237058-001
06-237059-001
76-800202-001
06-237058-001
06-237059-001