background image

V2.1.5 

Subject to technical changes. 

   

>>

 Operating & installation instructions bravour 

 

 

 

www.SmartHeat.de 

>> 

Electrical connection 

The module active cooling reveives the required electric power with the power supply of the heat pump. An additional 
power supply is not required. 

 
Hydraulic connection 

For hydraulic connection there are no differences to heat pumps without the module active cooling. The outgoing and 
backflow maintain their flow direction and are changing to cooling outflow and cooling backflow. Additional hydraulic 
connections for cooling function are not available. 
 

 

 

During start-up of the heat pump with module „Active Cooling“ take care of good 
flow in heating circuit! Have a look at the data sheet of the heat pump! If this flow 
is not ensured, there is the possibility of freezing of the heat exchanger, if the heat 
pump operates in cooling  mode during  start-up  unintentionally. This may lead to 
damages at the heat exchanger! A flow monitoring in the heating system must be 
guaranteed by the installation's operator. 

 

During  start-up  with  cold  heating  water  this  may  be  possible  also  at  sufficient 
volume flow! The water of heating circuit should not be colder than 25°C at the 
first start-up! 

 

4.2

 

Option N- Passive cooling 

General notes 

The  module  for  externally/internal  passive  cooling  extends  the  application  range  of  your  bravour  heat  pump  by  the 
function  to  cool  the  building  during  the  summer.  This  module  is  available  for  all  bravour-models  of  the  series  BW 
(brine/water) and WW (water/water). Cooling of the heating water during the summer months is achieved be transfer-
ring heat from the heating circuit to the brine circuit or the groundwater. When combining with a suitable heating and 
cooling  system  in  the  house  (combination  of  floor,  wall  and  ceiling  heating)  the  cooling  effect  can  be  realised  for  the 
desired  rooms.  As  the  module  for  passive  cooling  goes  without  using  the  refrigerating  circuit  of  the  heat  pump,  this 
gives a very reasonable possibility regarding energy consumption for cooling.  

 
Application areas 

The module for externally/internal passive cooling is based on a plate heat exchanger, as well as switching over compo-
nents (3-way-valve), which has to be installed externally/internal, and activating of cooling mode of the controller. Due 
to this combination it is possible, to cool down the heating water during the summer via the plate heat exchanger. In 
this case, the heat is taken up from the brine water or the ground-water and transported into the ground. The living 
spaces will be cooled and the ground heated up.  
By using the generously dimensioned heat exchanger, the separation of the heating water and brine water or ground-
water side continues to be kept. Filling of the heating side with antifreeze, like on the brine side, is not necessary. As 
the module for passive cooling operates without using the heat pump compressor, the occurring electricity consump-
tion is low by comparison. Only the two circulating pumps of the heating side as well as the brine water side or ground-
water side will be operated.  
 
As the function of the passive cooling is realised only via a heat exchange, a reduction  of the cooling  effect has to be 
assumed with increasing ground  or  ground-water temperature. The heat, transferred into the ground  will, at least in 
part, be stored and taken back when need for heating starts. This leads to an improvement of the capacity and annual 
operating data and can, by this, reduce the incurred electricity costs. In principle, the hot-water preparation has priority 
over the cooling function. 
 
The achievable cooling capacity cannot be given as a fixed value. It depends on the lay-out of the plate heat exchanger, 
as well as dimensioning of the cooling surfaces and the brine water or well system. A reduction of the cooling capacity 
during the summer can occur especially in brine water systems, as the ground continues to be heated up. With increas-
ing brine temperatures the transferable cooling capacity of the heat exchanger is decreasing.  

 

 
Specification-conform application 

Summary of Contents for bravour 008 BWi

Page 1: ...t to technical changes Operating installation instructions bravour www SmartHeat de 0 O Op pe er ra at ti in ng g i in ns st ta al ll la at ti io on n i in ns st tr ru uc ct ti io on ns s compact heat...

Page 2: ...ptimization according to ecological points of view The increasing performance as well as the use of coolants which are very harmful to the environment are to important criteria which had been taken in...

Page 3: ...embly_______________________________________________________________________________ 15 8 1 Connection at the side of the heat source _______________________________________________________ 15 8 2 Con...

Page 4: ...relevant VDE EN and IEC standards must be complied with for electrical connection of heat pumps The local connecting conditions of the utilities must be observed The operator must in particular make s...

Page 5: ...thin the usage frequency refer to the data sheet in Germany 50Hz In emergency situations decommission the heat pump resp switch in currentless condition main and control voltage Only expert approved s...

Page 6: ...uicker effective at the ground collector evaporator and the energy supply is made available as usable energy by the heat pump The heat emitting side of the SmartHeat bravour heat pump operates with a...

Page 7: ...50 100 100 o Carbon dioxide in ppm 5 5 10 10 5 5 10 10 o Ratio HCO3 SO4 2 1 1 Nitrate in ppm 100 100 Oxygen in ppm 1 1 8 8 1 1 8 8 o Ammonia in ppm 2 2 10 10 2 2 10 10 o Solute iron in ppm 0 2 0 2 0 5...

Page 8: ...pump device during production at the factory The indications for the following heat pumps are binding bravour serie BW i WW i The bravour module active cooling represents a firmly combined unit togeth...

Page 9: ...of the heat pump this gives a very reasonable possibility regarding energy consumption for cooling Application areas The module for externally internal passive cooling is based on a plate heat exchan...

Page 10: ...heat pump basic device A separate supply is not necessary Hydraulic connection There are no differences to the classic heat pump series without cooling module regarding the hydraulic connection of th...

Page 11: ...rmal and raise to a higher temperature level The terminals provided are in the chapter 8 3 Connection of the domestic hot water tank Proper use The module solar is an optional module for the upgrading...

Page 12: ...t de 11 5 Device view Fig perspective view Fig isometric view open Fig front view Fig side view right Deaerator Inverter Tank Control unit Operating unit Connection opening domestic water Refrigeratio...

Page 13: ...ect to technical changes Operating installation instructions bravour www SmartHeat de 12 Fig lower side plate right Fig Upper side plate right and left Fig rear plate Source inlet Source outlet Heat s...

Page 14: ...y perform commissioning and maintenance works and en sure free working space on all sides refer to the recommended minimum clearances The installation space must be dry and frost free and have a plane...

Page 15: ...ions bravour www SmartHeat de 14 Minimum clearances for the installation Fig Minimum dimensions for the installation of bravour Foundation Fig Foundation plan bravour 100cm 100cm 25cm 120cm Observe th...

Page 16: ...r to attain the values indicated on the data sheets resp in order to avoid malfunctions Compared to traditional incinerators of higher mass flows i e larger pipe cross sections and corresponding pump...

Page 17: ...in a complete failure of the heat pump After having performed the installation of the heating system fill bleed and squeeze off the heating system For the optimum connection comprehensive hydraulic a...

Page 18: ...g pressure 10 bar Operating temperature 90 C Heating buffer tank Material S 235 JR Operating pressure 3 bar Operating temperature 110 C Content domestic water 193 litre Content heating water 56 litre...

Page 19: ...cument the earth conductor resistance and the isolation resistance according to DIN VDE 0701 and DIN VDE 0702 These tests must be repeated according to the intervals applicable on site or according to...

Page 20: ...3 N PE 50Hz 400V Inverter 230 V 1 x supply heat pump 1 N PE 50Hz 230V 1 x supply control voltage 1 N PE 50Hz 230V 1 x heating coil 3 N PE 50Hz 400V or 1 N PE 50Hz 230V Flow monitor source The flow of...

Page 21: ...are cases in the heat pump itself Wrong settings on the controller may have similar effects The triggering of corresponding sensors and the signalling of a mal function serve to protect the system and...

Page 22: ...xceeded there is a risk of corrosion damages so that it is necessary to counteract such damages in a second step In the hardness stabilisation additives are added to the heating water by which the lim...

Page 23: ...roller instructions refer to part 2 of the operating instructions Furthermore you obtain information regarding the setting of the required room and hot water temperatures the setting of your own daily...

Page 24: ...necessary to have the system cleaned by an install er At this the condenser should be flushed contrary to the direction of flow In order to avoid that soiled heating water attains the heating system...

Page 25: ...of 10 kW in order to guarantee the required hot water preparation Of course there are sufficient reserves for the dry heating phase Expect to spend more money in electricity costs during the first he...

Page 26: ...it use flexible tubes for connection Freezing protection of the heat pump and the connection tubes should be ensured by the installer and user A minimum outgoing and backflow temperature of 25 C has t...

Page 27: ...V2 1 5 Subject to technical changes Operating installation instructions bravour www SmartHeat de 26 Hydraulic system bravour BW i...

Page 28: ...Operating installation instructions bravour Subject to technical changes V 2 1 5 www SmartHeat de 27 Hydraulic system bravour WW i...

Page 29: ...V2 1 5 Subject to technical changes Operating installation instructions bravour www SmartHeat de 28 Hydraulic system bravour DI...

Page 30: ...infold S 1 2 Four way brine circuit mainfold S 1 3 Five way brine circuit mainfold S 1 4 Six way brine circuit mainfold S 2 Safety set source S 5 Set natural cooling S 6 Safety assembly source H1 Safe...

Page 31: ...V2 1 5 Subject to technical changes Operating installation instructions bravour www SmartHeat de 30...

Page 32: ...Operating installation instructions bravour Subject to technical changes V 2 1 5 www SmartHeat de 31 15 Appendix EU declaration of conformity Technical data Terminal assignment plan...

Page 33: ......

Page 34: ...WWi R bravour 008 BWi N bravour 012 BWi N Richtlinien directives 2014 68 EU Druckger terichtlinie pressure equipment directive 2014 35 EU Niederspannungsrichtlinie Low voltage directive 2014 30 EU EM...

Reviews: