No.
Items
Parameters
Defaults
Description
37
Open Pulse Output
(1-1000)s
3
38
Average Beat Freq
(0-1)
1
0: Disabled 1: Enabled
39
Power Regulation Limit
(0-50)%
30
When the max. output duty ratio of
raise/drop speed relay is 0, the relay
does not output.
NOTE:
ID can be set via dial-up switch of terminal side; the IDs of modules which are connected to the same CAN bus
cannot be the same.
6
FUNCTION DESCRIPTION
6.1 INSTRUCTION
The function of HLS300 Power Share Module is to proportionally share active load to each
operating genset according to genset capacitance. When
―FIXLOAD‖ is active, the module works in
fixed power mode; otherwise the module works in power share mode. Press
button for 3s, and
it will enter into test mode, which is used to test relay output and indicator status.
6.2 FIXED POWER MODE
Target power can be set via the external device connected with terminal 16, 17, 18. When close
input is active, the module will adjust present power to target power and stabilize it between
△
f and
△
P.
6.3 POWER SHARE MODE
Multiple modules are connected with each other via CAN bus and operate in power share mode
together. Target power is an average of present power sums of these modules. When close input is
active, the module will adjust present power to target power and stabilize it between
△
f and
△
P.
6.4 TEST MODE
Press
button for 3s, and the module will enter into test mode and the lamp will illuminate, in the
mean time the other lamps irrelevant with relay output will illuminate. -P relay outputs and the
corresponding lamp will illuminate. In this mode, for every time to press
button, there will be a
relay output and the corresponding lamp will illuminate. The module will quit test mode after relay
output is finished (every time there will be only one relay output and the corresponding lamp will
illuminate). When it is in test mode, the module will automatically quit if there is no button pressed for
about 18s.
NOTE:
Test mode is prohibited when the module is operating (when close input is active).