![Smartgen HLS300 User Manual Download Page 10](http://html.mh-extra.com/html/smartgen/hls300/hls300_user-manual_1297465010.webp)
HLS300 Power Share Module User Manual
HLS300 Power Share Module Version 1.4 2019-05-16 Page 10 of 14
5
SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS
Table 7
– Module Configurable Parameters
No.
Items
Parameters
Defaults
Description
1
AC System
(0-1)
0
0: 3P3W, 1: 1P2W
2
Rated Voltage
(30-30000) V
400
3
Volt Trans.
(0-1)
0
0: Disabled 1: Enabled
4
Volt Trans. Primary Voltage (30-30000)V
100
5
Volt Trans. Secondary
Voltage
(30-1000)V
100
6
Over Volt
(0-1)
1
0: Disabled 1: Enabled
7
(100-120) %
115
Threshold
8
(100-120) %
113
Returned
9
(0-3600) s
3
Delay
10
Under Volt
(0-1)
1
0: Disabled 1: Enabled
11
(70-100) %
75
Threshold
12
(70-100) %
77
Returned
13
(0-3600) s
3
Delay
14
Over Freq
(0-1)
1
0: Disabled 1: Enabled
15
(100-120) %
110
Threshold
16
(100-120) %
104
Returned
17
(0-3600) s
3
Delay
18
Under Freq
(0-1)
1
0: Disabled 1: Enabled
19
(80-100) %
90
Threshold
20
(80-100) %
96
Returned
21
(0-3600) s
3
Delay
22
Loss Of Phase
(0-1)
1
0: Disabled 1: Enabled
23
Phase Rotation Monitor
(0-1)
1
0: Disabled 1: Enabled
24
CT Ratio/5
(5-6000)
500
25
Full Load Rated Current
(5-6000)A
500
26
Rated Power
(0-6000)kW
500
27
Reverse Power Threshold
(0-20)%
10
28
Reverse Power Delay
(1-20)s
3
29
Low Power Threshold
(0-20)%
10
30
Low Power Delay
(1-20)s
3
31
Address
(1-254)
1
32
Load Ramp Rate
(0-100)%
2
33
Load Ramp Rate Delay
Percentage
(1-40)%
15
34
Load Ramp Rate Delay
(0-30)s
5
35
Load
Parallel
Ramp
Minimum
(0-100)%
5
36
Load Feedback Percentage (0-100)%
50