![Smartgen HGMS62 User Manual Download Page 56](http://html1.mh-extra.com/html/smartgen/hgms62/hgms62_user-manual_1297538056.webp)
HGMS62 Split Type Genset Controller User Manual Page 56 of 58
14.14
SCANIA
It is suitable for S6 engine control module. Engine type is DC9, DC12, and DC16.
Table 39 – B1 Connector
Terminals of controller
B1 connector
Remark
Fuel relay output
3
Set aux. output 1 as “Fuel Output”.
Crank relay output
-
Connect to starter coil directly.
CAN(H)
9
Using impedance 120Ω connecting line.
CAN(L)
10
Using impedance 120Ω connecting line.
Engine type:
SCANIA.
14.15
VOLVO EDC3
Suitable engine control model is TAD1240, TAD1241, and TAD1242.
Table 40 – “Stand alone” Connector
Terminals of controller
“Stand alone” connector
Remark
Fuel relay output
H
Crank relay output
E
Aux. output 2
P
Set aux. output 2 as “ECU Power”.
Table 41 – “Data bus” Connector
Terminals of controller
“Data bus” connector
Remark
CAN(H)
1
Using impedance 120Ω connecting line.
CAN(L)
2
Using impedance 120Ω connecting line.
Engine type:
VOLVO.
NOTE:
When this engine type is selected, preheating time should be set to at least 3 seconds.
14.16
VOLVO EDC4
Suitable engine types are TD520, TAD520 (optional), TD720, TAD720 (optional), TAD721, TAD722, and
TAD732.
Table 42 – Connector
Terminals of controller
Connector
Remark
Fuel relay output
Expanded 30A relay, and
relay offers battery voltage
to Terminal 14. Fuse is
16A.
Crank relay output
-
Connect to starter coil directly.
1
Connected to battery negative.
CAN(H)
12
Using impedance 120Ω connecting line.
CAN(L)
13
Using impedance 120Ω connecting line.
Engine type:
VOLVO-EDC4.