HGMS62 Split Type Genset Controller User Manual Page 16 of 58
No.
Warnings
Description
Sequence
signal.
19 Transfer Failure
When breaker close/open fails and transfer failure warning is enabled,
controller will send warning alarm signal.
20 Temp. Sensor Open
When temperature sensor is open and open action selects “Warning”,
controller will send warning alarm signal.
21 High Temp.
When temperature value is higher that threshold, controller will send
warning alarm signal.
22 Low Temp.
When temperature value is lower that threshold, controller will send
warning alarm signal.
23
Oil Pressure Sensor
Open
When oil pressure sensor is open and open action selects “Warning”,
controller will send warning alarm signal.
24 Low Oil Pressure
When oil pressure value is lower than threshold, controller will send
warning alarm signal.
25 Level Sensor Open
When level sensor is open and open action selects “Warning”, controller
will send warning alarm signal.
26 Low Level
When level value is lower than threshold, controller will send warning
alarm signal.
27 Aux. Sensor 1 Open
When aux. sensor 1 is open, and open action selects “Warning”,
controller will send warning alarm signal.
28 Aux. Sensor 1 High
When aux. sensor 1 value is higher that threshold, controller will send
warning alarm signal.
29 Aux. Sensor 1 Low
When aux. sensor 1 value is lower that threshold, controller will send
warning alarm signal.
30 Aux. Sensor 2 Open
When aux. sensor 2 is open, and open action selects “Warning”,
controller will send warning alarm signal.
31 Aux. Sensor 2 High
When aux. sensor 2 value is higher that threshold, controller will send
warning alarm signal.
32 Aux. Sensor 2 Low
When aux. sensor 2 value is lower that threshold, controller will send
warning alarm signal.
33 Input Warning
When digital warning input is active, controller will send warning alarm
signal.