HGMS62 Split Type Genset Controller User Manual Page 32 of 58
No.
Items
Range
Default
Description
2
Module Address
(1-254)
1
Controller address in remote monitoring.
3
Language
(0-2)
0
0: Simplified Chinese; 1: English; 2:
Others.
4
Password
(0-65535)
00318
The password for entering advanced
parameter setting.
5
LCD Light-on
(0-3600) s
300
LCD is always illuminated when it is 0.
6
Mains Page Display
(0-1)
1
0: 4 parameters 1: 8 parameters
7
Pressure Unit
(0-1)
0
0: psi 1:bar
8
Date and Time
/
Display time of master control module:
YY:MM:DD (WEEK); HH:MM:SS.
9
ECU Run Time Display (0-1)
1
0: Disable; 1: Enable.
Schedule and Maintenance Setting
1
Scheduled Run
(0-1)
0
0: Disable; 1: Enable.
2
Scheduled Not Run
(0-1)
0
0: Disable; 1: Enable.
3
Maintenance Set
(0-1)
0
0: Disable; 1: Enable.
Analog Sensor Setting
Temperature Sensor
1
Curve Type
(0-15)
8
SGD. See Table 16.
2
Open Action
(0-2)
0
0: Warning; 1: Shutdown; 2: None.
3
Over High Shutdown
(0-1)
1
0: Disable; 1: Enable.
(-50-300)ºC
98
When external temperature value is
higher than it, high temp shutdown will
be issued. This value only begins to
judge after safety delay is over.
(0-3600)s
3
Confirm time for high temperature
shutdown detection.
4
Over High Warning
(0-1)
1
0: Disable; 1: Enable.
(-50-300)ºC
95
When external temperature value is
higher than it, high temp warning will be
issued. This value only begins to judge
after safety delay is over.
(-50-300)ºC
93
Return value: when external temperature
value is less than or equal to it, warning
will be removed.
(0-3600)s
5
Confirm time for high temperature
warning detection.
5
Over Low Warning
(0-1)
0
0: Disable; 1: Enable.
(-50-300)ºC
70
When external temperature value is
lower than it, low temp warning will be
issued. This value only begins to judge
after safety delay is over.