HGM9580 BUS TIE BUS PARALLEL UNIT
HGM9580 Bus Tie Bus Parallel Unit ISSUE 2014-02-16 Version 1.0 Page 22 of 33
No.
Items
Parameters
Defaults
Description
Flexible Output Ports
Flexible Output Port 1
1
Contents Setting
(0~239)
44
Bus 1 OK. See Form 2
2
Active Type
(0~1)
0
0:Normally open;
1:Normally close
Flexible Output Port 2
1
Contents Setting
(0~239)
48
Common Alarm. See Form 2
2
Active Type
(0~1)
0
0:Normally open;
1:Normally close
Flexible Output Port 3
1
Contents Setting
(0~239)
46
Bus 2 OK. See form 2
2
Active Type
(0~1)
0
0:Normally open;
1:Normally close
Flexible Output Port 4
1
Contents Setting
(0~239)
47
Synchronizing. See form 2
2
Active Type
(0~1)
0
0:Normally open;
1:Normally close
Flexible Output Port 5
1
Contents Setting
(0~239)
30
Open Bus Output. See form 2
2
Active Type
(0~1)
0
0:Normally open;
1:Normally close
Flexible Output Port 6
1
Contents Setting
(0~239)
29
Close Bus Output. See form 2
2
Active Type
(0~1)
0
0:Normally open;
1:Normally close
Flexible Output Port 7
1
Contents Setting
(0~239)
0
Not Used. See form 2
2
Active Type
(0~1)
0
0:Normally open;
1:Normally close
Flexible Output Port 8
1
Contents Setting
(0~239)
0
Not Used. See form 2
2
Active Type
(0~1)
0
0:Normally open;
1:Normally close
Sync Setting
1
MSC ID
(0-31)
1
It is the ID mark of the MSC
communication internet. All the MSC
ID should be unique.
2
Dead Bus Volt
(10-50)V
30
It is considered Bus no power when
Bus voltage is lower than dead Bus
voltage.
3
Slip Frequency
(0-1.00)Hz
0.10
Adjust bus frequency and enable it
greater than the other bus frequency.
When slip frequency is 0:
If the frequency difference is greater
than 0.1Hz, then the frequency will be