HGM9580 BUS TIE BUS PARALLEL UNIT
HGM9580 Bus Tie Bus Parallel Unit ISSUE 2014-02-16 Version 1.0 Page 20 of 33
7 SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS
7.1 CONTENTS AND SCOPES OF PARAMETERS
Form 1
No.
Items
Parameters
Defaults
Description
Battery Setting
1
Rated Voltage
(0-60.0)V
24.0
Standard
for
checking
battery
over/under voltage.
2
Over Voltage
(0-200)%
120%
Setting
value
is
rated
voltag
e’s
percentage,
return
value
(default:
115%) and delay value (default: 60s)
can be set.
3
Under Voltage
(0-200)%
85%
Setting
value
is
rated
voltage
’s
percentage, return value (default: 90%)
and delay value (default: 60s) can be
set.
Bus Setting
1
AC System
(0~3)
0
0: 3P4W; 1: 3P3W;
2: 2P3W; 3: 1P2W.
2
Volt. Trans.(PT)
(0-1)
0
0: Disable; 1:Enable
Switch Setting
1
Close Time
(0~20.0)s
5.0
Pulse width of switch on. When it is 0,
means output constantly.
2
Open Time
(0~20.0)s
3.0
Pulse width of switch off.
Module Setting
1
Power On Mode
(0~1)
0
0:
Manual mode
1:
Auto mode
2
Module Address
(1~254)
1
Controller’s address during remote
sensing.
3
Stop Bit
(0~1)
0
0: 2 stop bits; 1: 1 stop bit
4
Language
(0~2)
0
0: Simplified Chinese 1: English
2: Others
5
Password
(0~65535)
00318
For entering advanced parameters
setting.
Flexible Input Ports
Flexible Input Port 1
1
Contents Setting
(0~50)
28
Remote OnLoad. See form 3
2
Active Type
(0~1)
0
0: Closed to active
1: Open to active
Flexible Input Port 2
1
Contents Setting
(0~50)
0
User defined. See form 3
2
Active Type
(0~1)
0
0: Closed to active
1: Open to active
3
Arming
(0~2)
2
0: From paralleling
1: Always 2:Never