HGM9510 GENSET PARALLEL UNIT
HGM9510 Genset Parallel Unit ISSUE 2013-08-06 Version 1.1 Page 28 of 65
8 SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS
8.1 CONTENTS AND SCOPES OF PARAMETERS
Form 1
No.
Items
Parameters
Defaults
Description
Timer Setting
1
Start Delay
(0~3600)s
5
Time from mains abnormal or remote
start signal is active to start genset.
2
Stop Delay
(0~3600)s
30
Time from mains normal or remote start
signal is inactive to stop genset.
3
Preheat Delay
(0~3600)s
0
Time of pre-powering heat plug before
starter is powered up.
4
Cranking Time
(3~60)s
8
Time of starter power on
5
Crank Rest Time
(3~60)s
10
The waiting time before second power
up when engine start fail.
6
Safety On Delay
(0-3600)s
10
Alarms for low oil pressure, high
temperature,
under
speed,
under
frequency /voltage, charge fail are
inactive.
7
Start Idle Time
(0~3600)s
10
Idle running time of genset when
starting.
8
Warming Up Time
(0~3600)s
30
Warming up time between genset switch
on and high speed running.
9
Cooling Time
(0~3600)s
60
Radiating time before genset stop, after
it unloads.
10
Stop Idle Time
(0~3600)s
10
Idle running time when genset stop.
11
ETS Solenoid Hold (0~3600)s
20
Stop electromagnet’s power on time
when genset is stopping.
12
Fail to Stop Delay
(0~3600)s
0
Time between over of genset idle delay
and stopped when “ETS time” is set as
0;
Time between over of ETS hold delay
and stopped when “ETS Hold output
t
ime” is not 0.
13
After Stop Time
(0~3600)s
0
Time between genset stopped and
standby
Engine Setting
1
Engine Type
(0~39)
0
Default:
Conventional
Engine(not
J1939)
When connected to J1939 engine,
choose the corresponding type.
2
Flywheel Teeth
(10~300)
118
Tooth number of the engine, for judging