![Smartgen HGM6100N Series User Manual Download Page 38](http://html1.mh-extra.com/html/smartgen/hgm6100n-series/hgm6100n-series_user-manual_1297517038.webp)
HGM6100N Series Genset Controller User Manual Page 38 of 47
current must be 5A. Besides, the phase of CT and input voltage must be correct, or the sampling
current and active power may be incorrect.
NOTES:
A. Icom must connect to battery cathode of the controller.
B. When there is load current, open circuit is inhibited in the CT secondary side.
5)
Withstand Voltage Test
When the controller has been installed in the control panel, during the test please disconnect
all the terminals, in case high voltage damages the controller.