HGM6100N Series Genset Controller User Manual Page 23 of 47
No.
Items
Range
Default
Description
74(69)
Temp. Sensor Open
Circuit Action
(0-2)
1
0: Not used; 1: Warning; 2: Shutdown
75(70)
Oil Pressure Sensor
Open Circuit Action
(0-2)
1
76(71)
Disconnect
Oil
Pressure Delay
(0-20.0)s
0.0
When disconnect conditions include oil
pressure and engine oil pressure is higher
than disconnect oil pressure delay, the genset
is regarded as start successfully and starter
will disconnect.
77(72) Scheduled Run
(0-1)
0
0: Disabled; 1: Enabled.
78(73) Scheduled Period
(0-1)
0
Circulate condition: monthly, weekly and daily
can be selected.
Start time and duration can be set.
79(74) Auto Start Inhibited
(0-1)
0
0: Disabled; 1: Enabled.
80(75) Scheduled Period
(0-2)
0
Circulate condition: monthly, weekly and daily
can be selected.
Don’t start time and duration can be set.
81(76) Overload Action
(0-2)
0
0 Not used; 1 Warn; 2 Shutdown
When power is higher than preset value and
duration exceeds than delay, over power
warning is active. Return and delay value can
be set.
82(77) Start Interface
(0-1)
0
0: Disabled; 1: Enabled.
Start interface delay can be set.
83(78)
Maintenance
Password
(0-9999)
0
Enter password interface of maintenance
configuration.
84(79) Date/Time
Set the date/time of controller.
85(80)
94(89)
Flexible Sensor Curve
Type
(0-2)
0
0 User-defined temperature sensor
1 User-defined pressure sensor
2 User-defined level sensor
Choose sensor which need to be set, input
every point (8 points need to be input)
resistance and corresponding value(or
current, voltage) of curve.
86(81) Engine Type
(0-39)
0
0: Conventional Genset
NOTE:
It is only
suitable
for
HGM6100CAN.
87(82) SPN Alarm Version
(0-3)
0
SPN Alarm Version
88(83) Custom Theme
(0-2)
0
0: Default Theme;
1: OEM Plant Theme; 2:
Terminal Users Theme
89(84)
85(80)
Fuel Output Time
(1-60)s
1
It is the time of the genset fuel output during
power on.