4 OPERATION
4.1 KEY FUNCTION
Stop/ Reset
Can stop generator under mode of Manual/Auto;
Can reset alarming under Stop;
To test panel indicators are OK or not, pressing this
key at least 3 seconds;
During stopping process, press this again can stop
generator immediately.
Start
To start genset under Manual or Auto mode.
Manual
Pressing this key will set the module into manual
mode.
Automatic
Pressing this key will set the module into automatic
mode.
Running with load
Pressing and controller is under manual testing
mode.
Under this mode, genset will run with load automatic
when gens are normal. (HGM6110KC without)
Set/ Confirm
Enters into Set menu after pressing this, and can shift
cursor to confirm.
Page up
/increase
Screen pages turning;
Shift cursor and increase its position no. in setting.
Page down
/decrease
Screen pages turning;
Shift cursor and decrease its position no. in setting.
4.2 AUTOMATIC OPERATION
This mode is activated by pressing the
. LED indicator is illuminating beside the
button confirms this action.
Sequence of Auto Start,
a) HGM6120KC, When Mains is abnormal (over and under voltage, or miss
phase), enters into mains
“abnormal delay” and LCD display count down time.
When mains abnormal delay is over, enter into
“start delay”.
b) HGM6110KC, entries into
“start delay” as soon as “Remote Start” is input valid.
c)
“Count down” of start delay is displayed in LCD.
d) When start delay is over, preheat relay is outputting (if be equipped),
“preheat
start delay XX s
” is displayed in LCD.