other equipment.
4) Alternating current input
HGM6100K series controller to external input current transformer, electric
current transformer side must be 5A, while the current transformers for
phases and the phase of the input voltage must be correct, otherwise the
current and sampling the active power may be incorrect.
Note:
A. ICOM must connect battery anode power controllers.
B. When the load current, the transformer secondary side is strictly open
circuit.
5) Pressure test
When the controller has been installed in the control panel, if you will, please
put pressure test controller terminals all disconnected, lest high-pressured
into and damaged controller.
13 FAULT FINDING
Symptom
Possible Remedy
Generator inoperative
Check the battery and wiring to the unit.
Check the DC supply.
Check the DC fuse.
Generator shutdown
Check water/cylinder temperature whether or
not too high.
Check AC generator voltage.
Check the DC fuse.
Emergency shutdown
If an Emergency shutdown switch is not fitted,
ensure that a positive is connected to the
emergency shutdown input.
Check emergency shutdown switch is
functioning correctly.
Check wiring is not open circuit.
Low oil Pressure alarm (after
crank success)
Check engine oil pressure.
Check oil pressure switch/sensor and wiring.
Check configured polarity (if applicable) is
correct.
High Temp. alarm (after crank
success)
Check engine temperature.
Check switch/sensor and wiring.
Check configured polarity (if applicable) is
correct.
Shutdown fault operates
Check relevant switch and wiring of fault
indicated on LCD display.
Check configuration of input.