HGM400N Series Genset Controller User Manual Page 23 of 38
No.
Items
Range
Default
Description
signal via configurable input port)
85 Gen Over Volt Warn
(30-620)V
253
When genset voltage is over the point,
generator over voltage is active. When the
point is 620V, it does not detect over voltage
signal.
86 Gen Under Volt Warn
(30-620)V
193
When generator voltage is under the point,
generator under voltage is active. When the
point is 30V, it does not detect under voltage
signal.
87 Gen Over Freq Warn
(0-75.0)Hz
55.0
When generator frequency is over the point,
over frequency is active, gen over frequency
signal will be sent.
88 Gen Under Freq Warn
(0-75.0)Hz
42.0
When generator frequency is lower than the
point, under frequency is active, gen under
frequency signal will be sent.
89
Gen Over Current Warn
Percentage
(50-130)%
110
When load current is over the point, over
current is active. When this value is 0, warn
alarm signal won’t be sent.
90 High Temp. Warn
(80-140)°C
95
When the temperature value of the external
temperature sensor exceeds the set value,
“High Temperature” timer is initiated. Detecting
only after safety on delay has expired. If the set
value is 140, high temperature signal will not
be sent (this only concerns external
temperature sensor, not high temperature
signal via config. input port).
91 Low OP Warn
(0-400)kPa
124
When the external pressure sensor value falls
below this set value, “Low Oil Pressure” timer is
initiated. Detecting only after safety on delay
has expired. If the set value is 0, low oil
pressure signal will not be sent (this only
concerns pressure sensor and does not
concern low oil pressure warning signal via
configurable input port)
92 Aux. Sensor Warn
(80-140)°C
(0-400)kPa
(0-100)%
95
Respective corresponding with 90 temp.
sensor, 91 pressure sensor and 84 level sensor
in this table.
93 Gen Over Volt Delay
(0-20.0)s
10.0
When generator voltage exceeds shutdown
value and last for a while, gen over volt
shutdown is active.
94 Gen Over Freq Delay
(0-20.0)s
2.0
When generator frequency exceeds shutdown
value and last for a while, gen over freq
shutdown is active.