HFC6100LT Fan Controller User Manual Page 12 of 24
No.
Function
Cable Size
Remark
16 COM2
1.5mm
2
PWM 1-4 output common
ports
Connect to positive of
battery.
17 PWM Output 1
1.0mm
2
B+ is supplied by 16 points,
rated 8A
Transistor output rated 1A.
18 PWM Output 2
1.0mm
2
19 PWM Output 3
1.0mm
2
20 PWM Output 4
1.0mm
2
21 Aux. Input 1
1.0mm
2
Connect to GND(B-)
22 Aux. Input 2
1.0mm
2
Connect to GND(B-)
23 Aux. Input 3
1.0mm
2
Connect to GND(B-)
24 Aux. Input 4
1.0mm
2
Connect to GND(B-)
25 Aux. Input 5
1.0mm
2
Connect to GND(B-)
26 Aux. Input 6
1.0mm
2
Connect to GND(B-)
27 Aux. Input 7
1.0mm
2
Connect to GND(B-)
28 Aux. Input 8
1.0mm
2
Connect to GND(B-)
29 Aux. Input Common Port
The controller interior has been connected to power input B-.
30 Aux. Input 9
1.0mm
2
Connect to GND(B-)
31 Aux. Input 10
1.0mm
2
Connect to GND(B-)
32 Aux. Input 11
1.0mm
2
Connect to GND(B-)
33 Aux. Input 12
1.0mm
2
Connect to GND(B-)
34 Aux. Input 13
1.0mm
2
Connect to GND(B-)
35 Aux. Input 14
1.0mm
2
Connect to GND(B-)
36 Aux. Input 15
1.0mm
2
Connect to GND(B-)
37 Aux. Input 16
1.0mm
2
Connect to GND(B-)
38 Aux. Input 17
1.0mm
2
Connect to GND(B-)
39 Aux. Input 18
1.0mm
2
Connect to GND(B-)
40 Aux. Input Common Port
The controller interior has been connected to power input B-.
41 RS485+
0.5mm
2
Impedance-120Ω shielding wire is recommended and
its single end grounded.
42 RS485-
0.5mm
2
43 Terminal Resistor (120Ω)
0.5mm
2
If impedance-120Ω is needed, short connected
terminal 41
、
43.
44 Sensor 1 Input
1.0mm
2
Connect to temp. sensor 1.
45 Sensor 2 Input
1.0mm
2
Connect to temp. sensor 2.
46 Sensor 3 Input
1.0mm
2
Connect to temp. sensor 3.
47 Sensor 4 Input
1.0mm
2
Connect to temp. sensor 4.
48 Sensor 5 Input
1.0mm
2
Connect to temp. sensor 5.
49 Sensor Common Port
/
Sensor common port
The controller interior has been connected to power
input B-.