HAT530N ATS CONTROLLER Page 8 of 19
press
button to save the delay adjustment. All the indicators flash 5 times and return to
the normal test mode.
f)
If there is no need to set the parameter, press
button and hold it for more than 3s, all the
indicators will flash 5 times and return to the normal test mode;
Table 4 – Panel Parameter Setting
Parameter
No.
Setting Items
Settings & No.
Default
Parameter
Indicators
Setting
Indicators
1
Main Use
1
:
1# Power
Supply
1
:
1# Power
Supply
Flash once
Flash once
2
:
2# Power
Supply
Flash twice
3:
Mutual
Back-up
Flash 3 times
2
AC Line system
1: 3P4W
1: 3P4W
Flash twice
Flash once
2: 2P3W
Flash twice
3: Single phase
Flash 3 times
4: 3P3W
Flash 4 times
3
Auto Trans.
Auto Restore
1: Auto trans.
Non restore
2: Auto trans.
auto restore
Flash
3
times
Flash once
2: Auto trans.
auto restore
Flash twice
4
Remote
Adjustment
1:
Remote
adjustment
enable
1:
Remote
adjustment
enable
Flash
4
times
Flash once
2:
Remote
adjustment
disable
Flash twice
5
Delay Value of
Factory Default
Flash
5
times
Flash once
6
Delay Adjustment
1: 1# Power
abnormal delay Adjust
the
potentiometer
on back panel
Flash
6
times
Flash once
1: 2# Power
abnormal delay
Note 1: Each time the controller is power on, the main use status of the controller can be judged by the following three
conditions.
If the 1# power indicator flashes 3 times rapidly, the #1 power is main use.