Smartgen HAT530N User Manual Download Page 15

                                                     

 

HAT530N ATS CONTROLLER                                                                                                    Page 15 of 19

 

9

 

ATS POWER SUPPLY 

The power of ATS is supplied by controller, as long as one power is normal, this can ensure ATS power 
supply normally and can be transferred properly.   
Users should select power supply voltage (phase voltage or line voltage) based on ATS type. If choose 
phase  voltage,  connect  the  phase  voltage  of  1#  and  2#  (e.g.  A  phase)  to  normally  close  (Pin3)  and 
normally  open  (Pin1)  contact  of  auxiliary  output  1;  connect  N  phase  of  1#  and  2#  to  normally  close 
(Pin4) and normally open (Pin6) contact of auxiliary output 2. And then connect the common output of 
auxiliary  output  1  and  auxiliary  output  2  to  ATS  power  supplies.  When  controller  power  is  ON,  the 
default configuration of auxiliary output 1 is "ATS power A" while auxiliary output 2 is "ATS power N". If 
the  ATS  power  supplied  by  Line  Voltage,  same  procedures  as  above  but  change  phase  N  to  phase 
voltage and the auxiliary output 2 should be configured as “ATS power B”. Parameters can be set via PC 
software. Wiring diagrams are shown as following:   

   

                             

 

Fig. 4 - ATS phase voltage power supply                    Fig. 5 - ATS line voltage power supply 

NOTE: 

If there is no need to control ATS Power Supply, then the above terminals are not connected and the Auxiliary 

Output 1 and Auxiliary Output 2 should be set as “Not used”. If the Auxiliary output 1 and Auxiliary Output 2 are used for 
something function other than the “ATS Power Supply”, corresponding function items should be set. 

Summary of Contents for HAT530N

Page 1: ...HAT530N ATS CONTROLLER USER MANUAL ...

Page 2: ...spective companies SmartGen Technology reserves the right to change the contents of this document without prior notice Table 1 Software Version Date Version Note 2016 07 04 1 0 Original release 2018 05 25 1 1 Modify function of terminal 1 as normally open and terminal 3 as normally close 2019 05 22 1 2 Add AtyS d wiring diagram 2020 04 16 1 3 Add Auto Trans Auto Restore Auto Trans Non restore func...

Page 3: ...ARAMETTER SETTING 7 5 1 BUTTONS AND INDICATORS OF PARAMETER SETTIN 7 5 2 PARAMETER SETTING 7 6 PARAMETER CONFIGERATION 10 6 1 PARAMETERS TABLE 10 6 2 OUTPUT FUNCTION DESCRIPTION 12 7 OPERATION CONTROL 12 8 DESCRIPTION OF CONNECTING TERMINALS 13 8 1 BACK PANEL 13 8 2 FUNCTION DESCRIPTION OF WIRING TERMINALS 14 9 ATS POWER SUPPLY 15 10 TYPICAL WIRING DIAGRAM 16 11 INSTALLATION 18 12 FAULT FINDING 19...

Page 4: ...tware using SG72 module USB to LINK or other converse module The voltage normal delay of 1 or 2 can be set in 0 60 seconds and the Genset start delay can be set in 0 3600 seconds The voltage abnormal delay of 1 or 2 can be set in 0 60 seconds and the Genset stop delay can be set in 0 3600 seconds 1 Master Auto Manual Each Backup and 2 Master can be set via controller front panel to realize power s...

Page 5: ...olts free output AUX OUTPUT 1 16A AC250V Volts free output AUX OUTPUT 2 16A AC250V Volts free output Gen Start Relay 7A AC250V Volts free output 1 Close Input COM2 connect is active 2 Close Input COM2 connect is active Forced Breaking Input COM2 connect is active Communication LINK interface MODBUS Protocol Case Dimensions 139mmx120mmx50mm Panel Cutout 130mmx111mm Working Temperature 25 70 C Worki...

Page 6: ...hen 2 power state is abnormal off when there is no 2 power 1 Close Indicator It is illuminated when 1 power auxiliary contactor is active while off when it is deactivated 2 Close Indicator It is illuminated when 2 power auxiliary contact is active while off when it is deactivated Auto Mode Indicator It is illuminated when the controller is in auto mode while off the controller is in manual mode Ma...

Page 7: ... into parameter No 2 to check the status and it circles in order c If set AC system as 2P3W press button the indicator of parameter items is distinguished while the indicator of parameter items is illuminated then enter into the setting status d Press button to adjust the number to set parameter press button and the setting No will increase 1 After the parameter setting is done then press button t...

Page 8: ...W 1 3P4W Flash twice Flash once 2 2P3W Flash twice 3 Single phase Flash 3 times 4 3P3W Flash 4 times 3 Auto Trans Auto Restore 1 Auto trans Non restore 2 Auto trans auto restore Flash 3 times Flash once 2 Auto trans auto restore Flash twice 4 Remote Adjustment 1 Remote adjustment enable 1 Remote adjustment enable Flash 4 times Flash once 2 Remote adjustment disable Flash twice 5 Delay Value of Fac...

Page 9: ...and 2 close indicator flash 3 times rapidly at the same time it is auto trans auto restore status Note 4 When the remote adjustment is disabled PC cannot write parameter configuration to host computer Note 5 The factory default value is 1 power and 2 power abnormal delay for 5s the genset will stop delay for 90s Note 6 1 power abnormal delay adjust the potentiometer on back panel of 1 power normal...

Page 10: ...output pulse 07 Transfer Interval 0 60 s 1 It is the delay from 1 power open to 2 power close or from 2 power open to 1 power close 08 Exceed Transfer 0 20 0 s 0 0 It is the extra output delay of the close relay after the closing signal has received 09 Start Delay 0 3600 s 1 When voltage is abnormal start delay begins start signal is initiated after the delay has expired 10 Stop Delay 0 3600 s 90 ...

Page 11: ... One Breaking 1 No Breaking 30 Aux Output 1 0 23 20 More details please refer to the following OUTPUT FUNCTION DESCRIPTION 31 Aux Output 2 0 23 23 More details please refer to the following OUTPUT FUNCTION DESCRIPTION NOTE1 Parameters above are configured via PC software of SmartGen The PC programming connection is to use LINK interface of SG72 module connecting with LINK interface of controller N...

Page 12: ... Close Status Output The close status of 1 switch 17 2 Close Status Output The close status of 2 switch 18 Reserved 19 Reserved 20 ATS Power A Phase ATS power supply 21 ATS Power B Phase 22 ATS Power C Phase 23 ATS Power N Phase 7 OPERATION CONTROL When controller is running pressing key can set the controller as Auto mode or Manual mode indicated by automatic and manual indicators In Auto mode co...

Page 13: ...HAT530N ATS CONTROLLER Page 13 of 19 8 DESCRIPTION OF CONNECTING TERMINALS 8 1 BACK PANEL Fig 3 HAT530N Rare Panel Drawing ...

Page 14: ...tact output Normally Open Output Rated 10A 10 COM1 Output COM of close switch and open switch COM1 11 GEN Start Volt free relay contact output Normally Close Output Rated 7A 12 13 A1 1 AC 3 phase 4 wire voltage input For single phase only connect A1 N1 14 B1 15 C1 16 N1 17 1 Close Input Detection of 1 ATS closing status auxiliary contact input Connect COM2 is active 18 2 Close Input Detection of 2...

Page 15: ...liary output 2 to ATS power supplies When controller power is ON the default configuration of auxiliary output 1 is ATS power A while auxiliary output 2 is ATS power N If the ATS power supplied by Line Voltage same procedures as above but change phase N to phase voltage and the auxiliary output 2 should be configured as ATS power B Parameters can be set via PC software Wiring diagrams are shown as...

Page 16: ...HAT530N ATS CONTROLLER Page 16 of 19 10 TYPICAL WIRING DIAGRAM Fig 6 ATySM3s Wiring Diagram Fig 7 ATyS3s Wiring Diagram ...

Page 17: ... d Wiring Diagram NOTE The diagram is for reference only The actual wiring shall follow the ATS instruction Users should choose proper fuse capacity according to the actual power consumption If SOCOMEC VS is applied the Close delay and Open delay must be no less than 5s Default 5s ...

Page 18: ...ram Fig 11 Single phase 2 wire Wiring Diagram NOTE Above pictures take the AC 220V voltage as example If AC 110V voltage is applied in actual use please contact with SmartGen technical staff to get the specific wiring methods 11 INSTALLATION Fig 12 Installation Dimensions ...

Page 19: ... Check controller wring ATS not transfer Check ATS Check the connection wirings between the controller and the ATS Electrical parameters detection error Check controller wring Modify electrical parameters detection value PC software communication failure Check communication port setting and connections _________________________________ ...

Reviews: