HAT530N ATS CONTROLLER Page 12 of 19
No Priority" are changed to "0: 1# Master; 1: 2# Master; 2: Each Backup".
6.2
OUTPUT FUNCTION DESCRIPTION
Table 6 – Output Function Description
Items
Description
00. Not used
Invalid.
01. 1# Normal volt
It will output when1# voltage is normal.
02. 1# Abnormal volt
It will output when 1# voltage is abnormal.
03. 2# Normal volt
It will output when 2# voltages is normal.
04. 2# Abnormal volt
It will output when 2# voltages is abnormal.
05.1#2# Abnormal volt
It will output when 1#2# voltages are abnormal simultaneously.
06. Auto Mode
In will output in automatic mode.
07. Manual Mode
In will output in manual mode.
08. Gens start (N/O)
When generator starts output (Relay closed).
09. Gens start (N/C)
When generator starts output (Relay released).
10. 1# Close Output
1# Switch ON signal output.
11. Open Output
Switch OFF signal output.
12. 2# Close Output
2# Switch ON signal output.
13. Reserved
14. Reserved
15. Reserved
16. 1# Close Status Output
The close status of 1# switch.
17. 2# Close Status Output
The close status of 2# switch.
18. Reserved
19. Reserved
20. ATS Power A Phase
ATS power supply.
21. ATS Power B Phase
22. ATS Power C Phase
23. ATS Power N Phase
7
OPERATION CONTROL
When controller is running, pressing
key can set the controller as Auto mode or Manual mode
(indicated by automatic and manual indicators).
In Auto mode, controller can automatically transfer the load to 1# or 2# power. When it is set to Auto
Trans. Auto Restore, master power is normal, and controller will transfer to master power end in priority;
When it is set to Auto Trans. Non Restore, controller only transfers to backup power, and master power
transfer can only be controlled manually. Each Backup is for two powers to be backup; when 1# power
is abnormal, 2# is normal, then switch will transfer to 2# power supply, and vice versa. When it is set to
Each Backup, controller will not detect Auto Trans. Auto Restore setting.
In Manual mode, press
key, load will be transferred to 1# power supply; press
to disconnect
load supply; press
key, load will be transferred to 2# power supply.