4.3 INDICATOR DESCRIPTION
Table 5 Indicator Description
Indicators
Description
1# Power Indicator
Lamp illuminates: 1# power normal;
Lamp flashes: 1# power abnormal (over/under voltage, over/under
frequency and loss of phase);
Lamp off: 1# loss of power
2# Power Indicator
Lamp illuminates: 2# power normal;
Lamp flashes: 2# power abnormal (over/under voltage, over/under
frequency and loss of phase);
Lamp off: 2# loss of power
1# Main Indicator
Lamp illuminates: 1# Priority
Both illuminates
:“spare to each other
(auto throw, non restore)
”
2# Main Indicator
Lamp illuminates: 2# Priority
1# Close Indicator
Lamp illuminates: 1# Supply
2# Close Indicator
Lamp illuminates: 2# Supply
Alarm Indicator
Lamp illuminates: 1# or 2# Close/Open fault;
Lamp flashes: Auxiliary input alarm (Fire Reset input is active)
Auto Mode Indicator
Lamp illuminates: controller in Auto mode
Manual Mode Indicator
Lamp illuminates: controller in Manual mode
Lamp flashes: enter into parameter configuration mode
NOTE
: Lamp flash frequency: 1Hz
4.4 OPERATION
When the controller is normally working in manual mode, press
and it can make controller switch to
auto mode, and at this time auto indicator will illuminate.
If controller is in auto mode, press
and it can make controller transfer to manual mode. In manual
mode, press
and it can make load transfer to 1# power side; press
, and it can make load
transfer to 2# power side; press
, and ATS will transfer to neutral position (middle).
NOTE
: Power On Mode is decided by the last power down mode of the controller. If the controller is in manual mode at
power down, it will still in manual mode when power is on again.