BAC150CAN Battery Charger User Manual
BAC150CAN Battery Charger Version 1.0 2019-03-05 Page 10 of 13
Items
Default
Adjustable Range
Description
12V
24V
12V
24V
Auxiliary Input Port 3
(0~5)
0: Not Used;
1:
Shutdown;
The
battery
charger enters Standby Status
if the input is active.
2: Reserved;
3: Manual BOOST:
The battery charger enters
BOOST if the input is active.
4: Return to Float Mode:
The charger enters Float Mode
if the input is active.
5: Rated Voltage Output:
Charger shall output rated
voltage if the input is active.
Auxiliary Input Port
Delay
2.0s
(1.0~60.0)s
The corresponding action will
be active if the input is active
and the delay time has expired.
Auxiliary
Output
Port Setting
Charging
Failure
Waring
Mains
Failure
Warning
Multiple choices are
available.
Not Used;
Output over voltage warning;
Output under voltage warning;
External
temp.
sensor
short-circuit warning;
Charging failure warning
’;
Mains failure warning;
Auxiliary
Output
Port Delay
2.0s
(1.0~60.0)s
Output port is active after the
delay time.
Communication
Address
10
1~254
RS485 communication address
RS485 Baud Rate
0
(0~2)
1: stop bit;
0: 9600bps;
1: 19200bps;
2: 38400bps;
CAN Baud Rate
1
(0~2)
0:125kbps;
1: 250kbps;
2: 500kbps;
Battery Type
0
(0~4)
0: Lead-acid;
1: Li Battery;
2: Calcium-Calcium;
3: Power;
4: Users-defined;