BAC150CAN Battery Charger User Manual
BAC150CAN Battery Charger Version 1.0 2019-03-05 Page 9 of 13
Items
Default
Adjustable Range
Description
12V
24V
12V
24V
Under
Voltage
Return Value
12.5V
25.0V
(8~15)V
(16~30)V
The transit
ion voltage from ‘under
voltage’ to ‘normal voltage’
Under
Voltage
Return Delay
10s
(0~3600)s
Under voltage alarm will be
removed if the battery voltage has
exceeded the return value and the
delay time has expired.
Battery
Over
Voltage Warn
1
(0~1)
0: Disable; 1: Enable
Over Voltage Set
Value
16V
32V
(8~16)V
(16~32)V
Over voltage alarm will be initiated
if the battery voltage is above the
set value.
Over Voltage Delay 2s
(0~3600)s
Over voltage alarm will be initiated
if the battery voltage is above the
set value and the delay time has
expired.
Over
Voltage
Return Value
15.8V
31.6V
(8~16)V
(16~32)V
The transit
ion voltage from ‘over
voltage’ to ‘normal voltage’
Over
Voltage
Return Delay
10s
(0~3600)s
Over voltage alarm will be
removed if the battery voltage is
below the return value and the
delay time has expired.
Temperature
Sensor
1
(0~1)
0: Disable; 1: Enable
Temperature
Compensation
1
(0~1)
0: Disable; 1: Enable
Temperature
Compensation Set
Value
0.018V/
℃
0.036V/
℃
(0.010~0.
030)V/
℃
(0.020~0.
060)V/
℃
The Compensation of every 1
℃
change on 20
℃
basis.
High Temp. Warn
1
(0~1)
0: Disable; 1: Enable
High
Temp.
Set
Value
55
℃
(0~80)
℃
High Temp. alarm will be initiated
if the battery temperature has
exceeded the set value.
High Temp. Delay
0.5s
(0~60.0)s
High Temp. alarm will be
initiated
if
the
battery
temperature has exceeded the
set value and the delay time
has expired.
High Temp. Return
Value
50
℃
(0~80)
℃
The transition temperature from
High Temp. to Normal Temp.
High Temp. Return
Delay
1.0s
(0.0~60.0)s
High Temp. alarm will be
removed
if
the
battery
temperature has fallen below
the return value and the delay
time has expired.