5 TECHNICAL SPECIFICATIONS
Table 5: Technical specifications
Power supply
from internal BUS
Number of delta pressure inputs
1
Operating pressure
0 .. 1000 Pa
Proof pressure
15000 Pa
Burst pressure
20000 Pa
Pressure sensor accuracy on full
scale value
+- 0.5
%
FSS (+-5 Pa)
Recommended dimensions for
measuring pipes connection
inner diameter 4.0 .. 4.5 mm or
outer diameter 8.5 mm or
inner diameter 10.0 .. 10.5 mm
Max. power consumption
0.5 W
Dimensions (L x W x H)
90 x 18 x 60 mm
Weight
100 g
Ambient temperature
0 to 50
°
C
Ambient humidity
max. 95
%
, no condensation
Maximum altitude
2000 m
Mounting position
vertical
Transport and storage temperature
-20 to 60
°
C
Pollution degree
2
Protection class
IP 30
7