Longo programmable controller LPC-2.PW1
4 OPERATION
Module parameters can be read or written via Smarteh IDE software.
4.1 Parameters
If parameter is set to logical “1”, is considered to be active, enabled or set. If parameter has logical
value “0” is considered to be inactive, disabled or cleared.
Parameter can be a output, input, status or setting. Output and input parameters corresponds to the
physical output and input pins of the module. Status parameters are used for additional information
from the module, where setting parameters are used to select different settings on the module.
Output:
Q1 - PWM output
[OUT1]
:
Output setting.
Type: WORD
Raw to engineering data:
0 .. 10000 0.00 .. 100.00%
→
Q2 - PWM output
[OUT2]
:
Output setting.
Type: WORD
Raw to engineering data:
0 .. 10000 0.00 .. 100.00%
→
Q3 - PWM output
[OUT3]
:
Output setting.
Type: WORD
Raw to engineering data:
0 .. 10000 0.00 .. 100.00%
→
Q4 - PWM output
[OUT4]
:
Output setting.
Type: WORD
Raw to engineering data:
0 .. 10000 0.00 .. 100.00%
→
Setting:
Fade effect timer for Q1
[OUT1FadeTimer]
:
Parameter for adjusting the transition time
(fade effect) between 0% and 100% and vice versa on Q1.
Type: WORD
Raw to engineering data:
0 .. 10000 0 .. 10 s
→
Fade effect timer for Q2
[OUT2FadeTimer]
:
Parameter for adjusting the transition time
(fade effect) between 0% and 100% and vice versa on Q2.
Type: WORD
Raw to engineering data:
0 .. 10000 0 .. 10 s
→
Fade effect timer for Q3
[OUT3FadeTimer]
:
Parameter for adjusting the transition time
(fade effect) between 0% and 100% and vice versa on Q3.
Type: WORD
Raw to engineering data:
0 .. 10000 0 .. 10 s
→
Fade effect timer for Q4
[OUT4FadeTimer]
:
Parameter for adjusting the transition time
(fade effect) between 0% and 100% and vice versa on Q4.
Type: WORD
Raw to engineering data:
0 .. 10000 0 .. 10 s
→
4