Longo programmable controller LPC-2.CR1

4 OPERATION

Operation of the CR1 module is also dependent on parameters received on RS-485 communication 
channel.

Reader RFID field is active always when module is powered up. If tag is put inside RFID field, reader 
tries to resolve RFID tag code. If code is read successfully, module activates status 

iIDNew, 

generates a short beep, OK LED1 blinks and code is transmitted in 

iIDW1 - iIDW3

 status fields. In 

MCU application this code can be read out and authenticated. If code has appropriate rights, MCU 
should activate 

oOK

 command. If code is not authorized, MCU application should activate 

oFault 

command. Regarding command received, following action are triggered on module:

oOK 

    

-->

OK LED2 blink, short beep.

o

Fault  -->

Fault LED1 blink, long beep.

Either command is received or no command is received within 10 sec, module clears 

iIDNew

 status 

and waits for next RFID tag. While CR1 module is waiting for authorization response, new RFID tags  
can not be read.

4.1 Parameters

If parameter is set to logical “1”,   is considered to be active, enabled or set. If parameter has
logical value “0” is considered to be inactive, disabled, or cleared.

Parameter can be feedback or command. Parameter as feedback means that CR1 module is sending 
information to MCU. On the other hand, command represents request from MCU to module. 

Command:

ID Fault 

[oFault]

Command for rejecting authorization of RFID code.

ID OK 

[oOk]

Command for authorization of RFID code.

Buzzer 

[oBuzz]

While this command is active, buzzer is active.

'Fault' ID LED 

[oFaultLD]

While this command is active,  fault LED1 is set.

'OK' ID LED 

[oOkLD]

While this command is active, OK LED2 is set.

Card Type Select 

[oSelTyp]

:

 0   Emarine; 1   hitag.

 

Feedback:

RFID ID Word1 

[iDW1]

:

 Upper (most significant) third of RFID code.

RFID ID Word2 

[iDW2]

Middle third of RFID code.

RFID ID Word3 

[iDW3]

:

 Lower (least significant) third of RFID code.

New ID

 [iIDNew]

:

 When new RFID tag is recognized, this status is set active for 10sec or till

authorization command is received (

oOK

 or 

oFault

).

Communication

  [iComm]

:

  Normal state is “0”. If set, there is communication error or no

communication established.

'Up-right' TB 

[iUpRTB]

signal from button located up-right corner (this button is disabled

by default and can be enable in EPROM).

'Up-left' TB 

[iUpLTB]

signal from button located up-left corner (this button is disabled by

default and can be enable in EPROM).

4

Summary of Contents for LPC-2.CR1

Page 1: ...USER MANUAL Longo programmable controller LPC 2 CR1 Card Reader module Version 5 SMARTEH d o o Poljubinj 114 5220 Tolmin Slovenia Tel 386 0 5 388 44 00 e mail info smarteh si www smarteh si...

Page 2: ...Longo programmable controller LPC 2 CR1 Written by SMARTEH d o o Copyright 2016 SMARTEH d o o User Manual Document Version 005 June 2016 i...

Page 3: ...ransport or because of unconsidered corresponding regulations of the country where the module is installed This device must be connected properly by the provided connection scheme in this manual Misco...

Page 4: ...ntroller LPC 2 CR1 1 ABBREVIATIONS 1 2 DESCRIPTION 2 3 FEATURES 3 4 OPERATION 4 4 1 Parameters 4 5 INSTALLATION 5 5 1 Connection scheme 5 5 2 Mounting instructions 7 5 3 Module labeling 8 6 TECHNICAL...

Page 5: ...ontroller LPC 2 CR1 1 ABBREVIATIONS Sorted by order of appeareance in document RFID Radio frequency identification SOS Emergency call LED Light emitting diode DIP Dual in line package ID Identity MCU...

Page 6: ...ck opening turning light on If key card number is not valid the red LED blinks and a longer beep is generated Functionalities are controlled from MCU Controller is accompanied with Smarteh IDE applica...

Page 7: ...rammable controller LPC 2 CR1 3 FEATURES Figure 1 LPC 2 CR1 module Table 1 Technical data RFID reader OK LED Fault X LED Power LED Internal fault LED Internal built in buzzer Black or white glass poss...

Page 8: ...eter has logical value 0 is considered to be inactive disabled or cleared Parameter can be feedback or command Parameter as feedback means that CR1 module is sending information to MCU On the other ha...

Page 9: ...Longo programmable controller LPC 2 CR1 5 INSTALLATION 5 1 Connection scheme Figure 2 Connection scheme 5...

Page 10: ...ault X ON RFID key standard NOK or ID card number wrong OFF No tag in proximity LED2 green OK ON RFID key standard OK and ID card number valid OFF No tag in proximity LED5 red Communication ON RS 485...

Page 11: ...ule Bticino Living Light Gewiss Playbus System Vimar Plana Idea Tem Modul Soft Modul Line Master Frames of other vendors most probably suits as well but they were not verified by Smarteh Before instal...

Page 12: ...n panels Mounting of RFID panels into conductive metal frames is not allowed RFID panel should not be positioned close to conductive areas 1 Set the correct RS 485 address S1 switch for LPC 2 CR1 refe...

Page 13: ...ounting module 01 derivation code 001 version code reserved for future HW and or SW firmware upgrades 3 D C 01 10 is the date code 01 week and 10 year of production Label 2 descriptions 1 S N CR1 S9 1...

Page 14: ...Power consumption 1 5 W RFID type EM4100 125 kHz Manchester 64 read only HITAG2 UID read only Max reading distance 4 cm Dimensions W x H x D 75 x 49 x 29 mm Weight 40 g Ambient temperature 0 to 50 C A...

Page 15: ...umbers should be used LPC 2 CR1 Card Reader module LPC 2 CR1 EM black P N 225CR109V01001 LPC 2 CR1 Card Reader module LPC 2 CR1 EM white P N 225CR115V01W01 LPC 2 MC8 Main module LPC 2 MC8 P N 225MC813...

Page 16: ...describes all the changes to the document Date V Description 07 06 2016 5 General update 01 06 2014 4 Power consumption data update 01 02 2013 3 Technical update 01 07 2012 2 CGP General update 18 03...

Page 17: ...Longo programmable controller LPC 2 CR1 9 NOTES 13...