Longo Modbus Products LMP-1.MP2
Table 4: Digital Inputs
Memory
Variable description
Range
Values
10001
Communication status
0/1
Error/OK
10002
Normal/Economy status
0/1
Normal/Economy
10003
Local/Remote status
0/1
Local/Remote
10004
Heat Valve status
0/1
Closed/Open
10005
Cool Valve status
0/1
Closed/Open
10006
System ON/OFF status
0/1
ON/OFF
10007
Winter / Summer status
0/1
Winter/Summer
10008
4/2 pipe System status
0/1
4 pipe/2 pipe
10009
Not used
10010
Not used
10011
Not used
10012
Not used
10013
Not used
10014
PushButton Pressed Status
0/1
Off/On
10015
Enable Balcony Door sts.
0/1
Disable/Enable
10016
Enable Window status
0/1
Disable/Enable
Table 5: Input Registers
Memory
Variable description
Range
Values
30001
Max. Temp. Set val. [0.01°]
0 .. 10000
0.00 .. 100.00°C
30002
Min. Temp. Set val. [0.01°]
0 .. 10000
0.00 .. 100.00°C
30003
P regulation par.status
0 .. 100
0 .. 100
30004
I regulation par.status
0 .. 100
0 .. 100
30005
PI Deadband par. [0.01°]
0 .. 10000
0.00 .. 100.00 °C
30006
Not used
30007
Temp. Setpoint [0.01°]
0 .. 10000
0.00 .. 100.00 °C
30008
Act. Room Temp. [0.01°]
0 .. 10000
0.00 .. 100.00 °C
30009
Absolute PI out value
0 .. 10000
0 .. 10000
30010
Act. Light intensity [%]
0 .. 100
0 .. 100 %
8