Output Voltage Setting Table
SW No.
Battery Selector
Float Voltage
Power Supply
1
ON
OFF
OFF
2
*
ON
FF
O
3
*
*
ON
4
ON
OFF
OFF
ON
OFF
OFF
5
OFF
ON OFF
OFF ON OFF
6
OFF OFF OFF OFF
OFF
OFF
ON ON ON
12V
Output
15.0 14.6 14.2 13.8
13.5
13.2
13.8 13.5 13.2
24V
Output
30.0 29.2 28.4 27.6
27.0
26.4
27.6 27.0 26.4
Note:
Dip-SW No. 1, 2 and 3 are switched off automatically (regardless it is on/off), when Dip-SW No. 6
is switched on.
Float Volt
Bulk
/
Absorption Volt
Battery Type
Dip Switch Setting
12V
24V
12V 24V
SLA / GEL
SW 3 ON, SW 1,2,4,5,6 OFF
13.2 V
26.4V
14.2 V
28.4V
AGM / wet /
Starter
SW 2,5 ON, SW 1,3,4,6 OFF
13.5 V
27.0V
14.6 V
29.2V
Calcium
SW 1,4 ON, SW 2,3,5,6 OFF
13.8 V
27.6V
15.0 V
30.0V
Caution!
1)
The device is for indoor use, do not use the device near flammable materials
or in any location that may accumulate flammable fumes or gasses.
2)
Appliance shall only be used with rated voltage and frequency
3)
Hot surface when operating, especially at full load condition.
4)
Make sure the polarity is correct
5)
Do not locate the device on the top of the battery. Especially Flooded, Wet
type battery. It may generate gas vapor while charging.
6)
Do not charge non-rechargeable batteries.
7)
Use the appliance only in the described manner.
8)
Do not expose the device to a heat source, such as direct sunlight or
heating.
9)
Store the device in a dry and cool place
10)
Do not open, no user serviceable parts inside.