CHARACTERISTICS
Mechanical
Dimensions
117 x 73 x 27 mm (7 DIN modules), protection rating IP20
Mass
175 g not including accessories
Mounting
Magnetic for metallic surface or DIN rail with adapters supplied
Power Supply
Source
Built-in 2W
- Single-phase supply, between blue (N) and green (L1)
leads
Voltage
From 50 to 435 VAC between phase and neutral
Typical current
consumed
30 mA at 230 VAC
25 mA at 277 VAC
Electrical Characteristics
Voltage Input
Smart X: CAT IV 300 V (source of the installation of the LV* network)
Smart X + three-phase lead: CAT III 300 V (building’s LV* network)
Smart X + electrical socket: CAT II 300 V (LV* network load).
Single-phase with 2 leads or three-phase with 3 to 4 leads, max. volt
-
age 435 VAC between leads. Fuse protection 3AG FF 500 mA, breaking
capacity of 50 kA min. Input impedance 330 kΩ (kohm) per phase
Protection rating II.
* LV: Low-Voltage
Current Input
Three-phase measurement with 3 cables
ATO Sensors: from 0 to 125 AAC, max. diam. 16 mm
ART Sensors: at 50 Hz, max. 2 750 AAC per phase, max. diam. 125 mm
at 60 Hz, max. 2 300 AAC per phase, max. diam. 125 mm
Signals from 0 mVp to 500 mVp, tolerable overload 2 Vp
Frequency
50 Hz ± 0,5 Hz or 60 Hz ± 0,5 Hz
Weather Conditions
Use
Indoors
From 0 to 2 000 metres altitude
From 5 °C to 40 °C; 10 % to 80 % relative humidity
Storage
Indoors
From 0 to 10 000 meters altitude
From 5 °C to 40 °C ; 10 % to 80 % relative humidity
This product complies with French norms EN/CEI 61010-2-030, EN 61326-1:2013, EN 301 489-1 V2.2.0:2017, ETSI EN
301 489-3 V2.1.1:2017, ETSI EN 301 489-17:2017 V3.2.0, EN 62479:2010, ETSI EN 300 220-2 V3.1.1:2016, ETSI EN 300 328
V2.1.1:2016.
10