![SMA SUNNY ISLAND SIC40-MPT Technical Description Download Page 25](http://html1.mh-extra.com/html/sma/sunny-island-sic40-mpt/sunny-island-sic40-mpt_technical-description_1294206025.webp)
SMA Solar Technology AG
Electrical Connection
Technical Description
SIC40-TEN081110
25
7.
Tighten the lock nut of the cable screw connection.
5.5 Communication
The communication between the charge controller and the Sunny Island 5048/2012/2224 allows
the charge controller to be controlled in a coordinated manner and ensures the precise calculation
of the charge state in the Sunny Island without an additional battery current sensor resistor.
All important operating data of the charge controller can be read on the Sunny Island display. In
addition, the most important values are saved on the Sunny Island SD card (if available).
Up to four charge controllers can be connected in parallel to one Sunny Island system.
If the poles of the DC cables are reversed, replace the thermal fuses
If the DC cables are reversed when connecting, the thermal fuse will be irreparably
damaged. Proceed as described in section 9.1 "Replacing the Thermal Fuses" (Page 36)
to replace the thermal fuses.
Multicolored LED
Once the battery has been connected, the multicolored LED of the charge controller
illuminates red. If the LED does not illuminate, the poles of the DC cables are reversed
and the thermal fuses must be replaced. If this is not the case, the charge controller is
defective and must be replaced. In this case, contact the SMA Service Line. See section
14 "Contact" (Page 47).
DANGER!
Danger to life due to high voltages in the charge controller.
•
Only switch on the line circuit breaker and connect the cables to the battery once
all connections on the charge controller have been established.
SIC40-MPT 1
SIC40-MPT 2
SIC40-MPT 3
SIC40-MPT 4
Sunny Island
Summary of Contents for SUNNY ISLAND SIC40-MPT
Page 2: ......
Page 6: ...SMA Solar Technology AG 6 SIC40 TEN081110 Technical Description...
Page 48: ...Contact SMA Solar Technology AG 48 SIC40 TEN081110 Technical Description...
Page 49: ...SMA Solar Technology AG Contact Technical Description SIC40 TEN081110 49...
Page 50: ...Contact SMA Solar Technology AG 50 SIC40 TEN081110 Technical Description...