Installer Level Menu Guide
SI4248U Manual
52
Generator Settings (24)
TcycleFull
1 - 180
D
14
The TcycleFull parameter selects the number of days
between the last boost charge and the next full
charge cycle.
TcycleEqual
7 - 365
D
60
The TcycleEqual parameter selects the number of
days between the last boost-charge and the next
equalize charge.
SOCLim1
0 - 100
%
40
State of charge generator start
SOCLim2
0 - 100
%
30
State of charge load shedding
SOCLim3
0 - 100
%
20
State of charge system shutdown
TBatMax
0 - 55
°C
45
Maximun battery temperature
Name
Range/
Unit
Default
Description
GenControl
Manual,
Direct,
GenMan
Manual The GenControl parameter selects the type of gen-
erator control to be used with your system.
Manual
: Manual start type or no generator con-
nected.
Direct
: Two-wire start generator connected to the
dry contacts in the inverter.
GenMan
: GenMan option installed.
AmpacGen-
Max
2 - 60
AAC
10
The AmpGenMax Parameter should be set to about
85 % of the maximum AC current of your genera-
tor. In Charge Mode the Sunny Island 4248U will
then limit the total current (loads in the
Sunny Island) to this value in order to prevent the
generator from stalling.
Note:
If the load in the system is above this value in
Voltage Mode, the Sunny Island 4248U will not
switch to Charge Mode for the same reason.
Name
Range/
Unit
Default
Description