Installer Level Menu Guide
SI4248U Manual
50
Generator Meters (13)
Settings
Inverter Settings (22)
Battery Settings (23)
Name
Range/
Unit
Default
Description
VacGenerator
0 - 260
VAC
N/A
The VacGenerator menu displays the AC voltage at
the inverter generator input.
AmpacGenerat
0 - 60
AAC
N/A
The AmpacGenerator menu displays the AC current
at the inverter generator input.
FacGenerator
0 - 70
Hz
N/A
The FacGenerator menu displays the AC frequency
at the inverter generator input.
PacGenerator
0 - 20
kWAC
N/A
The PacGenerator menu displays the AC power at
the inverter generator input.
Name
Range/
Unit
Default
Description
VacNominal
105 - 130
VAC
120
The VacNominal parameter sets the nominal output
voltage of the inverter.
FacNominal
55 - 65
Hz
60
The FacNominal parameter sets the nominal output
frequency of the inverter.
Name
Range/
Unit
Default
Description
VdcBatNomi-
nal
42 - 48
VDC
48
The VdcBatNominal parameter sets the nominal
operating voltage of the inverter.
BatType
VRLA
FLA
VRLA
The BatType parameter selects the type of battery
used in the system.
VRLA
= Valve Regulated Lead Acid
FLA
= Flooded Lead Acid
This parameter needs to be set when the inverter is
first commissioned. Once the system is configured,
this parameter can only be changed after selecting
„Reset“ in „NewBattery“ (23-5).