SMA
Technologie AG
Technical data
Installation Guide
SB1100LV-11:SE2006
Page 39
dFac-Max
Maximum "grid frequency change" before the grid monitoring
system disconnects the device from the grid.
dZac-Max
Maximum "grid impedance change" before the grid monitoring
system disconnects the device from the grid.
E_Total
Total energy yield for the inverter. This change may be
necessary when you exchange the Sunny Boy and want to use
the data from the old device.
Fac-delta-
Fac-delta+
Maximum frequency, above (Fac-delta+) and below (Fac-delta-)
the mains frequency, before the mains monitoring system
disconnects the device from the mains supply.
Fac-Pderating
Frequency-dependent output limitation
Fac-Tavg
Averaging time of grid frequency gaging
h_Total
Total hours of operation for the inverter. This change may be
necessary when you exchange the Sunny Boy and want to use
the data from the old device.
I-Ni-Test
Setting the impulse for impedance monitoring. This parameter
only functions when the Sunny Boy is deactivated (disconnected
on the AC side) or in "Stopp" mode.
Inst.-Code
Parameters for self contained power system recognition can only
be changed after entering the "SMA grid guard" password.
LDVtgC
Compensation for the voltage drop in the cabling.
With this parameter, the voltage drop between the inverter and
the grid connection point is taken into account. The average
voltage over 10 minutes at the inverter connection must not
exceed the sum of ACVtgRPro plus LDVtgC. The parameter
LDVtgC is preset to 0 V for Germany. In grid areas in which the
additional surge voltage protection (see parameter ACVtgRPro)
is not required, the parameter LDVtgC is preset to 50 V. Thus, the
surge voltage protection is deactivated for these grid areas
(253 V + 50 V = 303 V) and only the fast cut-off via the Uac-
Max parameter intervenes.
Name
Explanation
Summary of Contents for Sunny Boy SB 1100LV
Page 2: ......
Page 8: ...Foreword SMA Technologie AG Page 8 SB1100LV 11 SE2006 Installation Guide ...
Page 10: ...Safety instructions SMA Technologie AG Page 10 SB1100LV 11 SE2006 Installation Guide ...
Page 32: ...Installation SMA Technologie AG Page 32 SB1100LV 11 SE2006 Installation Guide ...
Page 44: ...Technical data SMA Technologie AG Page 44 SB1100LV 11 SE2006 Installation Guide ...
Page 50: ...Replacing the varistors SMA Technologie AG Page 50 SB1100LV 11 SE2006 Installation Guide ...
Page 58: ...The communications interface SMA Technologie AG Page 58 SB1100LV 11 SE2006 Installation Guide ...
Page 61: ......