6 Mounting
SMA Solar Technology AG
Installation Manual
SCCP-JP_NR-IA-en-11
16
Requirements:
☐ Two persons must be available for disassembling the rear panel.
☐ The required mounting material must be available (see Section 5.1, page 13).
☐ A storage location for the enclosure parts must be available.
☐ The inverter must be sufficiently protected from inclement weather.
CAUTION
Danger of crushing caused by heavy, bulky rear panel
The rear panel of the inverter is heavy and bulky. Danger of crushing when the rear panel slips off or tilts Weight of
the roof: 20 kg.
• Wear suitable personal protective equipment for all work on the product.
• Always have two persons disassemble and mount the rear panel.
Procedure:
1.
DANGER
Danger to life from electric shock due to live voltage
Prior to performing any work on the inverter, disconnect it from voltage sources (see inverter installation
manual).
2. Secure the rear panel of the inverter from slipping off.
3. Unscrew all ten screws of the rear panel using a suitable
screwdriver (TX 30).
10x
4. Remove all screws from the rear panel and retain for later use.
5. Carefully pull the rear panel of the inverter cabinet approx.
80 mm to 100 mm towards you. Make sure that the hook fitting
cannot fall out.
Summary of Contents for CP-JP Series